If you want to use the Runtime Version of WinCC Fleixible on the PC where the S7 PCI315 card is plugged in,
 
If you want to use the Runtime Version of WinCC Fleixible on the PC where the S7 PCI315 card is plugged in,
 
you have to setup WinCC Fleixible in the follwing way.
 
you have to setup WinCC Fleixible in the follwing way.
In der Systemsteuerung wählen Sie in der <PC/PG Schnittstellenzuordnug> als Zugangspunkt der Applikation '''S7ONLINE''' aus.
+
From the control panel open the "Set PG/PC interface" dialogbox and select '''S7ONLINE''' and '''IBH S7-PCI315 Intern(MPI)'''.
Die <Benutze Schnittstellenparametrierung> stellen Sie auf '''IBH S7-PCI315 Intern(MPI)'''.
+
  
 
[[Image:S7-PI315_PC_PG_Eng.png|422px]]
 
[[Image:S7-PI315_PC_PG_Eng.png|422px]]
  
Im WinCC Projekt kann unter '''Verbindungen''' ein Verbindungsname vergeben werden, in unserem Beispiel '''S7-PCI315 Lokal'''.
+
Within WinCC in the project tree-item <Connections> now the connection has to be given a name, in our sample'''S7-PCI315 Lokal'''.
  
Als <Kommunikationstreiber> wählen Sie '''SIMATIC S7 300/400'''.Die <Schnittstelle> wird auf '''MPI/DP''' gestellt. Durch die Einstellung in der PC/PG Schnittselle wird intern der schnellste Zugriffsweg (S7 TCP/IP) verwendet, unabhängig davon welche Baudrate ausgewählt wird. Die Steuerungsparameter stellen Sie wie im screenshot ein:
+
As <Communication driver> '''SIMATIC S7 300/400''' has to be selected.
  
[[Image:S7-PI315_Verbindungen.png|813px]]
+
For <Interface> choose '''MPI/DP'''.
 +
Through the setting of the PG/PC interface internal the fasted communication way (S7 TCP/IP) will be choosen, independent what Baud rate is selected.
 +
 
 +
Verify the parameters of the PLC:
 +
 
 +
[[Image:S7-PI315_Connections.png|810px]]
 
The configuration of the connection is now completed and you can continue with defining your Tags.
 
The configuration of the connection is now completed and you can continue with defining your Tags.

Revision as of 14:48, 29 June 2012

WinCC Flexible Runtime local with IBHsoftec S7-PCI315

If you want to use the Runtime Version of WinCC Fleixible on the PC where the S7 PCI315 card is plugged in, you have to setup WinCC Fleixible in the follwing way. From the control panel open the "Set PG/PC interface" dialogbox and select S7ONLINE and IBH S7-PCI315 Intern(MPI).

S7-PI315 PC PG Eng.png

Within WinCC in the project tree-item <Connections> now the connection has to be given a name, in our sampleS7-PCI315 Lokal.

As <Communication driver> SIMATIC S7 300/400 has to be selected.

For <Interface> choose MPI/DP. Through the setting of the PG/PC interface internal the fasted communication way (S7 TCP/IP) will be choosen, independent what Baud rate is selected.

Verify the parameters of the PLC:

S7-PI315 Connections.png The configuration of the connection is now completed and you can continue with defining your Tags.