IBHNet:Settings within STEP®7 without IBHNet driver

From IBHsoftec Wiki English
Revision as of 09:39, 25 June 2012 by Jonas (Talk | contribs)

(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

Starting with firmware version 2.146 of the IBH Link S7++ and the IBH Link S7++ HS, it is possible to communicate without the use of the IBHNet driver. In S7 for Windows® the support is already fully integrated. If STEP®7 is used, the IBH Link can be entered in the project as dummy station. If the PG is networked over Ethernet TCP/IP, all stations behind the IBH Link can be accessed MPI® as well as via PROFIBUS.

  • Via "PLC ⇒ Edit Ethernet Node..." the IBH Link can be searched, identified and configured. The procedure is identical to any SIMATIC® node.
  • If the MPI® and the IP-address of the IBH Link are known, it can be integrated in a S7 Project as PLC 6ES7 412-2EK06-0AB0 V6.0 via MPI®.


PropS7NetproEng.PNG


  • If the PROFIBUS and the IP-address of the IBH Link are known, it can be integrated in a S7 Project as PLC 6ES7 412-2EK06-0AB0 V6.0 via PROFIBUS.


PropS7NetproDPEng.PNG


  • The PG station must be networked with the ethernet. The ISO protocol must be unselected.


PropS7EthernetEng.PNG


  • If no automatic PG assignment is selected, the protocol "TCP/IP ⇒ Your Network card" must be selected in "Set PG/PC interface".