Starting with firmware version 2.146 of the IBH Link S7++ and the IBH Link S7++ HS, it is possible to communicate without the use of the IBHNet driver. In S7 for Windows® the support is already fully integrated. If STEP®7 is used, the IBH Link can be entered in the project as dummy station. If the PG is networked over Ethernet TCP/IP, all stations behind the IBH Link can be accessed MPI® as well as via PROFIBUS.
- Via "PLC ⇒ Edit Ethernet Node..." the IBH Link can be searched, identified and configured. The procedure is identical to any SIMATIC® node.
- If the MPI® and the IP-address of the IBH Link are known, it can be integrated in a S7 Project as PLC 6ES7 412-2EK06-0AB0 V6.0 via MPI®.
- If the PROFIBUS and the IP-address of the IBH Link are known, it can be integrated in a S7 Project as PLC 6ES7 412-2EK06-0AB0 V6.0 via PROFIBUS.
- The PG station must be networked with the ethernet. The ISO protocol must be unselected.
- If no automatic PG assignment is selected, the protocol "TCP/IP ⇒ Your Network card" must be selected in "Set PG/PC interface".