IBHLink S5++:SIMATIC® S5 Elipse SCADA

From IBHsoftec Wiki English
Revision as of 15:17, 18 June 2012 by Axel (Talk | contribs)

(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

It is possible to realize a connection from a PC with Elipse SCADA to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.

Example

In the following example a configuration with Elipse SCADA is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S7++ 192.168.10.125

MPI addresses:

Station Address
IBHLink S7++ 17
S7-300/S7-400 station 2

Configuration:

The ethernet communication driver for S7-300/400 named MProt.dll must be selected witin the Application Organizer: Elipse driver.png

Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address> Elipse driver settings.png


Enter the IP Address of the IBH LinkS7 ++ and choose port 102:

Elipse driver settings ethernet.png

Now the N an P Parameters must be set. The description you'll find within the helpfile <mprot_us.chm>
In the sample DB1.DB0 is chosen:

Elipse P paramter.png Elipse N paramter.png

The configuration is now completed and the Tags can be used:
Elipse tags.png