IBHLink S5++:SIMATIC® S5 Elipse SCADA

From IBHsoftec Wiki English
Jump to: navigation, search

It is possible to realize a connection from a PC with Elipse SCADA to a SIMATIC S5 PLC over ethernet using an IBHLink S5++ as gateway.

Example

In the following example a configuration with Elipse SCADA is shown. The HMI station is connected to the IBHLink S5++ via an Ethernet connection. The IBHLink S5++ itself is connected to the AS511 port of the SIMATIC S5 PLC. Communication parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses: IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S5++ 192.168.10.125

Operation with S7 HMI devices: For the operation with S7 HMI devices the following settings need to be made:

IP address of the PLC IP address of the IBH Link S5++
Rack number of the PLC 0
Slot number of the PLC 2
MPI address of the PLC 2

Configuration:

The ethernet communication driver for S7-300/400 named MProt.dll must be selected witin the Application Organizer: Elipse driver.png

Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address> Elipse driver settings.png


Enter the IP Address of the IBH LinkS5 ++ and choose port 102:

Elipse driver settings ethernet.png
Now the N an P Parameters must be set. The description you'll find within the helpfile <mprot_us.chm>
In the sample DB1.DB0 is chosen:

Elipse P paramter.png Elipse N paramter.png

The configuration is now completed and the Tags can be used:
Elipse tags.png