WinCC Flexible Runtime local with IBHsoftec S7-PCI315
If you want to use the Runtime Version of WinCC Fleixible on the PC where the S7 PCI315 card is plugged in, you have to setup WinCC Fleixible in the follwing way. From the control panel open the "Set PG/PC interface" dialogbox and select S7ONLINE and IBH S7-PCI315 Intern(MPI).
Within WinCC in the project tree-item <Connections> now the connection has to be given a name, in our sampleS7-PCI315 Lokal.
As <Communication driver> SIMATIC S7 300/400 has to be selected.
For <Interface> choose MPI/DP. Through the setting of the PG/PC interface internal the fasted communication way (S7 TCP/IP) will be choosen, independent what Baud rate is selected.
Verify the parameters of the PLC:
The configuration of the connection is now completed and you can continue with defining your Tags.