The IBHLink S7++ / IBH Link S7++HS is engineered as PLC station in NetPro and networked via MPI®
 
The IBHLink S7++ / IBH Link S7++HS is engineered as PLC station in NetPro and networked via MPI®
 
or Profibus with the PLC.
 
or Profibus with the PLC.
 +
 
MLFB: 6ES7 412-2EK06-0AB0 V6.0 Rack 0, Slot 2
 
MLFB: 6ES7 412-2EK06-0AB0 V6.0 Rack 0, Slot 2
  
Line 31: Line 32:
 
[[Image:Clock_Master.png‎|537px]]
 
[[Image:Clock_Master.png‎|537px]]
  
In der angeschlossenen CPU muss die Uhrsynchronisation wie folgt eingestellt werden:
+
Within the properties of the networked PLC you have to set up the synchronisation as follows:
  
[[Image:SCPU_Slave.png‎|537px]]
+
[[Image:Clock_Slave.png‎|537px]]
  
Die Projektierung wird in den IBH Link S7++/ IBH Link S7++HS und in die angeschlossene(n) CPU(s) geladen:
+
The Network project needs to be loaded in the IBH Link S7++/ IBH Link S7++HS and the networked PLC:
  
[[Image:Station_laden.png‎|761px]]
+
[[Image:Download_stations.png‎|656px]]

Revision as of 15:08, 10 December 2012


Projected Time Synchronisation with IBHLink S7++ or IBHLink S7++ HS.

Projected Time Synchronisation with NetPro

Within IBH Link setting Routing has to be activated :

IBH Link Routing eng.png


The IBHLink S7++ / IBH Link S7++HS is engineered as PLC station in NetPro and networked via MPI® or Profibus with the PLC.

MLFB: 6ES7 412-2EK06-0AB0 V6.0 Rack 0, Slot 2

Netpro.png

The IP and MPI/Profibus addresses need to be set equal to the addresses within the IBH Link S7++ / S7++ HS.

MPI Address.png

Ethernet address.png

The selected NTP(Network Time Protocol) Server must be reachable.

NTP Address.png


Set the Synchronisation <On the MPI> to Master:

Clock Master.png

Within the properties of the networked PLC you have to set up the synchronisation as follows:

Clock Slave.png

The Network project needs to be loaded in the IBH Link S7++/ IBH Link S7++HS and the networked PLC:

Download stations.png