Difference between revisions of "S7-SoftPLC:STEP®7 Hardwareconfiguration"

From IBHsoftec Wiki English
Jump to: navigation, search
(Created page with "For the hardware configuration only the shown modules should be used. Configuring the process images will be made via the interface of the ''S7-SoftPLC''. In the STEP<sup>®</...")
 
Line 6: Line 6:
 
{| class="wikitable"
 
{| class="wikitable"
 
|-
 
|-
|style="width: 20em"| 6ES7 315-1AF03-0AB0 V1.0||style="width: 20em"| S7-SoftPLC 315 ohne PROFIBUS®
+
|style="width: 20em"| 6ES7 315-1AF03-0AB0 V1.0||style="width: 20em"| S7-SoftPLC 315 without PROFIBUS®
 
|-
 
|-
 
| 6ES7 315-2AG10-0AB0 V2.0 || S7-SoftPLC 315 with PROFIBUS®
 
| 6ES7 315-2AG10-0AB0 V2.0 || S7-SoftPLC 315 with PROFIBUS®

Revision as of 11:31, 23 January 2013

For the hardware configuration only the shown modules should be used. Configuring the process images will be made via the interface of the S7-SoftPLC. In the STEP®7 hardware configuration only the Ethernet-CP parameters, the PROFIBUS®-CP parameters and the CPU parameters (like clock flags or time OBs) can be set.


Purchase order numbers compatible to S7-SoftPLC:

6ES7 315-1AF03-0AB0 V1.0 S7-SoftPLC 315 without PROFIBUS®
6ES7 315-2AG10-0AB0 V2.0 S7-SoftPLC 315 with PROFIBUS®
6ES7 315-2AG10-0AB0 V2.6 S7-SoftPLC 315 with PROFIBUS® and TIA
6ES7 315-2EH13-0AB0 V2.6 S7-SoftPLC 315 with PROFINET® and TIA
6ES7 416-1XJ02-0AB0 V1.0 S7-SoftPLC 416 without PROFIBUS®
6ES7 416-2XK02-0AB0 V1.1 S7-SoftPLC 416 with PROFIBUS®
6ES7 416-2XN05-0AB0 V5.1 S7-SoftPLC 416 with PROFIBUS® and TIA
6ES7 416-3ER05-0AB0 V5.1 S7-SoftPLC 416 with PROFINET® and TIA

Sample configuration for S7-SoftPLC 315

Slot Order-No / Firmware Name
2 6ES7 315-1AF03-0AB0 / V1.0 CPU 315

S7-SoftSPS 315 with Ethernet-CP

Slot Order-No / Firmware Name
2 6ES7 315-1AF03-0AB0 / V1.0 CPU 315
4 6GK7 343-1EX11-0XE0 / V2.0 CP 343-1

WARNING: SAVE CONFIGURATION DATA ON THE CPU NEEDS TO BE SELECTED.

S7-SoftPLC 315 with PROFIBUS®

Slot Order-No / Firmware Name
2 6ES7 315-2AG10-0AB0 CPU 315-2 DP

S7-SoftPLC 315 with PROFIBUS® and Ethernet-CP

Slot Order-No / Firmware Name
2 6ES7 315-2AG10-0AB0 CPU 315-2 DP
4 6GK7 343-1EX11-0XE0 / V2.0 CP 343-1


WARNING: SAVE CONFIGURATION DATA ON THE CPU NEEDS TO BE SELECTED.

Step7HW315.png

S7-SoftPLC 416

Slot Order-No / Firmware Name
2 6ES7 405-0DA00-0AA0 PS 405 4A
4 6ES7 416-1XJ02-0AB0 CPU 416-1

S7-SoftPLC 416 with Ethernet-CP

Slot Order-No / Firmware Name
1 6ES7 405-0DA00-0AA0 PS 405 4A
2 6ES7 416-1XJ02-0AB0 CPU 416-1
3 6GK7 443-1EX11-0XE0 / V1.1 CP 443-1

S7-SoftPLC 416 with PROFIBUS®

Slot Order-No / Firmware Name
1 6ES7 405-0DA00-0AA0 PS 405 4A
2 6ES7 416-2XK02-0AB0 CPU 416-2 DP

S7-SoftPLC 416 with PROFIBUS® and Ethernet-CP

Slot Order-No / Firmware Name
1 6ES7 405-0DA00-0AA0 PS 405 4A
2 6ES7 416-2XK02-0AB0 CPU 416-2 DP
3 6GK7 443-1EX11-0XE0 / V1.1 CP 443-1

Step7HW416.png