For the hardware configuration only the shown modules should be used. Configuring the process images will be made via the interface of the S7-SoftPLC. In the STEP®7 hardware configuration only the Ethernet-CP parameters, the PROFIBUS®-CP parameters and the CPU parameters (like clock flags or time OBs) can be set.
Purchase order numbers compatible to S7-SoftPLC:
6ES7 315-1AF03-0AB0 V1.0 |
S7-SoftPLC 315 without PROFIBUS®
|
6ES7 315-2AG10-0AB0 V2.0 |
S7-SoftPLC 315 with PROFIBUS®
|
6ES7 315-2AG10-0AB0 V2.6 |
S7-SoftPLC 315 with PROFIBUS® and TIA
|
6ES7 315-2EH13-0AB0 V2.6 |
S7-SoftPLC 315 with PROFINET® and TIA
|
6ES7 416-1XJ02-0AB0 V1.0 |
S7-SoftPLC 416 without PROFIBUS®
|
6ES7 416-2XK02-0AB0 V1.1 |
S7-SoftPLC 416 with PROFIBUS®
|
6ES7 416-2XN05-0AB0 V5.1 |
S7-SoftPLC 416 with PROFIBUS® and TIA
|
6ES7 416-3ER05-0AB0 V5.1 |
S7-SoftPLC 416 with PROFINET® and TIA
|
Sample configuration for S7-SoftPLC 315
Slot |
Order-No / Firmware |
Name
|
2 |
6ES7 315-1AF03-0AB0 / V1.0 |
CPU 315
|
S7-SoftSPS 315 with Ethernet-CP
Slot |
Order-No / Firmware |
Name
|
2 |
6ES7 315-1AF03-0AB0 / V1.0 |
CPU 315
|
4 |
6GK7 343-1EX11-0XE0 / V2.0 |
CP 343-1
|
WARNING: SAVE CONFIGURATION DATA ON THE CPU NEEDS TO BE SELECTED.
S7-SoftPLC 315 with PROFIBUS®
Slot |
Order-No / Firmware |
Name
|
2 |
6ES7 315-2AG10-0AB0 |
CPU 315-2 DP
|
S7-SoftPLC 315 with PROFIBUS® and Ethernet-CP
Slot |
Order-No / Firmware |
Name
|
2 |
6ES7 315-2AG10-0AB0 |
CPU 315-2 DP
|
4 |
6GK7 343-1EX11-0XE0 / V2.0 |
CP 343-1
|
WARNING: SAVE CONFIGURATION DATA ON THE CPU NEEDS TO BE SELECTED.
S7-SoftPLC 416
Slot |
Order-No / Firmware |
Name
|
1 |
6ES7 405-0DA00-0AA0 |
PS 405 4A
|
2 |
6ES7 416-1XJ02-0AB0 |
CPU 416-1
|
S7-SoftPLC 416 with Ethernet-CP
Slot |
Order-No / Firmware |
Name
|
1 |
6ES7 405-0DA00-0AA0 |
PS 405 4A
|
2 |
6ES7 416-1XJ02-0AB0 |
CPU 416-1
|
3 |
6GK7 443-1EX11-0XE0 / V1.1 |
CP 443-1
|
S7-SoftPLC 416 with PROFIBUS®
Slot |
Order-No / Firmware |
Name
|
1 |
6ES7 405-0DA00-0AA0 |
PS 405 4A
|
2 |
6ES7 416-2XK02-0AB0 |
CPU 416-2 DP
|
S7-SoftPLC 416 with PROFIBUS® and Ethernet-CP
Slot |
Order-No / Firmware |
Name
|
1 |
6ES7 405-0DA00-0AA0 |
PS 405 4A
|
2 |
6ES7 416-2XK02-0AB0 |
CPU 416-2 DP
|
3 |
6GK7 443-1EX11-0XE0 / V1.1 |
CP 443-1
|