Difference between revisions of "S7-SoftPLC:cifX Basic configuration"
From IBHsoftec Wiki English
Line 3: | Line 3: | ||
If no PROFIBUS<sup>®</sup> is used, the configuration has to be executed with the System Configurator SyCon.NET of Hilscher company. | If no PROFIBUS<sup>®</sup> is used, the configuration has to be executed with the System Configurator SyCon.NET of Hilscher company. | ||
− | * [[ | + | * [[S7-SoftPLC:Configuration of cifX card with SYCON.NET|Configuring the cifX-card with the System Configurator]] |
How the driver is integrated into ''S7-SoftPLC'' is part of these instructions: | How the driver is integrated into ''S7-SoftPLC'' is part of these instructions: |
Revision as of 11:36, 17 January 2013
The basic configuration features of the cifX-cards are set here.
If no PROFIBUS® is used, the configuration has to be executed with the System Configurator SyCon.NET of Hilscher company.
How the driver is integrated into S7-SoftPLC is part of these instructions:
Using the SFC
Command SFC
Via the SFC 1008 it is possible to read multiple informations from the cifX-cards
CALL | SFC/FC 1008 | |
COMMAND | := 0 | //INPUT DWORD |
BOARD | := 0 | //INPUT BYTE |
CHANNEL | := 0 | //INPUT BYTE |
DATA | := P#DB10.DBX0.0 BYTE 100 | //INPUT ANY |
RET_VAL | := MW 0 | //RESULT INT |
Command | Length ANY-Pointer Dataarea | Description |
---|---|---|
1 | 24 | Reads the SystemInformation from cifX-card |
2 | 48 | Reads the SystemInfoBlock from cifX-card |
3 | Reads the SystemChannelBlock from cifX-card | |
4 | 8 | Reads the SystemControlBlock from cifX-card |
5 | 64 | Reads the SystemStatusBlock from cifX-card |
6 | 165 | Reads the ChannelInformation from cifX-card |
7 | 64 | Reads the CommonStatusBlock from cifX-card |
Busdiagnose SFC
Via the SFC 1009 the CommonStatusBlock is read
CALL | SFC/FC 1009 | |
BOARD | := 0 | //INPUT BYTE |
CHANNEL | := 0 | //INPUT BYTE |
RET_VAL | := MW 0 | //RESULT INT |
COMCOS | := MD 2 | //OUTPUT DWORD |
COMSTATE | := MD 6 | //OUTPUT DWORD |
COMERROR | := MD 10 | //OUTPUT DWORD |
SLAVESTATE | := MD 14 | //OUTPUT DWORD |
SLAVEERROR | := MD 18 | //OUTPUT DWORD |
SLAVECONF | := MD 22 | //OUTPUT DWORD |
SLAVEACTIVE | := MD 26 | //OUTPUT DWORD |
SLAVEFAULT | := MD 30 | //OUTPUT DWORD |
Message SFC
Via SFC 1010 Messages are sent to cifX-card
CALL | SFC/FC 1010 | |
SEND | := 0 | //INPUT BOOL |
BOARD | := 0 | //INPUT BYTE |
CHANNEL | := 0 | //INPUT BYTE |
TIMEOUT | := 5 | //OUTPUT DWORD |
INDATA | := P#DB10.DBX0.0 BYTE 20 | //INPUT ANY |
OUTDATA | := P#DB0.DBX20.0 BYTE 20 | //INPUT ANY |
RET_VAL | := MW 0 | //RESULT INT |
BUSY | := M2.0 | //OUTPUT BOOL |
NDR | := M2.1 | //OUTPUT BOOL |
ERROR | := M2.2 | //OUTPUT BOOL |
SFC 14
Via the SFC "DPRD_DAT" inputs can be read out of the cifX dualport RAM
CALL | SFC/FC 14 | |
LADDR | := W#16#100 | //INPUT WORD |
RET_VAL | := MW 0 | //RESULT INT |
RECORD | := P#M 100.0 BYTE 1 | //OUTPUT ANY |
Parameter | Type of data | Description |
---|---|---|
LADDR | WORD | Start address of inputs to be read |
RET_VAL | INT | 0 on success |
RECORD | ANY | ANY-Pointer to readout data |
SFC 15
Via the SFC "DPWR_DAT" outputs can be written into the cifX dualport RAM
CALL | SFC/FC 15 | |
LADDR | := W#16#100 | //INPUT WORD |
RECORD | := P#M 102.0 BYTE 1 | //INPUT ANY |
RET_VAL | := MW 0 | //RESULT INT |
Parameter | Type of data | Description |
---|---|---|
LADDR | WORD | Start address of outputs to be written |
RECORD | ANY | ANY-Pointer on data to be written |
RET_VAL | INT | 0 on success |