Enable PU/OP functions via PROFIBUS® DP

Allows a PU-communication via the PROFIBUS® to S7-SoftPLC. Some OP's (as e.g. OP3) use PU-communication for data exchange with the PLC, so that these panels can be used as well.*


Don't stop fiedbus on PLC stop (only for PU functions via DP)

Prevents, that the bus is stopped at PLC Stop by the watchdog. The outputs are programmed set to 0. The Hilscher card is initialised when starting the PLC or changing the system data. At RUN/STOP, no further initialisation is performed. If online functions are used via PROFIBUS® with S7 for Windows® or STEP®7, this option has to be activated.


Display SFC14

Displays SFC14.


Display SFC15

Displays SFC15.


Activate DPV-1 functions on the PROFIBUS®

Allows sending and receiving DPV1 functions to DPV1 slaves. SFB52 and SFB53 are available for DPV1 services.*


PROFIBUS® configuration applies to BoardNumber:

The PROFIBUS® configurated system data applies to the CIF card number listed here.


Default

Sets all settings back to their default values.


Settings

In the section [CIFCFG] PROFIBUS® specific settings are conducted. The settings are necessary, if the bus configuration is to be created with the S7 for Windows® hardware configuration or the STEP®7 hardware configuration.

Key name Value range Default value Description
BoardNumber 0 .. 3 0 Board number reported by the Hilscher driver

0 = Board 0, 1 = Board 1, etc.

OnlineDP 0 / 1 0 1=Allows a PU-communication via the PROFIBUS® to S7-SoftPLC. Some OP's (as e.g. OP3) use PU-communication for data exchange with the PLC, so that these panels can be used as well.1)
SFC14 0 / 1 0 1=Show SFC14 from this driver

diagnostic capabilities = every slave (detailed diagnostics).1)

SFC15 0 / 1 0 1=Show SFC15 from this driver

diagnostic capabilities = every slave (detailed diagnostics).1)

DPV1 0 / 1 0 1=Allows sending and receiving DPV1 functions to DVP1 slaves. SFB52 and SFB53 are available for DPV1 services.1)
NoStop 0 / 1 0 Prevents, that the bus is stopped at PLC Stop by the watchdog. The outputs are programed set to 0. At RUN/STOP, no further initialisation is performed. Activating this parameter prevents, that a running PU-connection is disrupted when stopping the PLC. Has to be switched on in CIF30Dn.DLL driver section as well.

1) The bus configuration has to be created with S7 for Windows® hardware configuration or STEP®7 hardware configuration.
The configuration has to be created exclusively with General Station Description (GSD)