S7-SoftPLC:Diagnostic buffer entries
The chart below shows the differences to S7-hardware PLC diagnostic buffer entries:
Diagnostic buffer entries | Driver | Description |
---|---|---|
0xA000 | CIF PROFIBUS® | CIF-PROFIBUS®-card could not be initialized. |
0xA001 | CIF PROFIBUS® | Timeout during startup. |
0xA002 | CIF PROFIBUS® | Parameter inappropriate for CIF-Task |
0xA003 | CIF PROFIBUS® | Timeout during hot start |
0xA004 | CIF PROFIBUS® | Error when reading CIF-Firmware info |
0xA005 | CIF PROFIBUS® | Error when reading CIF-driver status |
0xA006 | CIF PROFIBUS® | Error when writing a message into the CIF-card |
0xA007 | CIF PROFIBUS® | Error when writing a message from the CIF-card |
0xA008 | CIF PROFIBUS® | Fehler bei PROFIBUS® Diagnose (PG)
CIF-Fehlercode |
0xA009 | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (PU)
CIF-error code |
0xA00A | CIF PROFIBUS® | Timeout during hot start |
0xA00B | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (PU)
CIF-error code |
0xA00C | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (PU)
CIF-error code |
0xA00D | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (PU)
CIF-error code |
0xA00E | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (PU)
CIF-error code |
0xA00F | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (PU)
CIF-error code |
0xA010 | CIF PROFIBUS® | No CIF-driver installed |
0xA011 | CIF PROFIBUS® | CIF-PROFIBUS®-card could not be initialized |
0xA012 | CIF PROFIBUS® | CIF-PROFIBUS®-card not available |
0xA013 | CIF PROFIBUS® | Bus parameters for slaves could not be set |
0xA014 | CIF PROFIBUS® | Parameterisation of the CIF-PROFIBUS®-card with SDB-Daten failed |
0xA015 | MPI® | MPI®-telegram error |
0xA016 | CIF PROFIBUS® | Error in PU communication via PROFIBUS® |
0xA017 | CIF PROFIBUS® | Error in PU communication via PROFIBUS® |
0xA018 | CIF PROFIBUS® | Error in PU communication via PROFIBUS® |
0xA019 | CIF PROFIBUS® | Timeout in input data exchange with the CIF-card during SFC DPRD_DAT |
0xA01A | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (SFC/SFB)
CIF-error code |
0xA01B | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (SFC/SFB)
CIF-error code |
0xA01C | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (SFC/SFB)
CIF-error code |
0xA01D | CIF PROFIBUS® | Error at PROFIBUS® Diagnostics (SFC/SFB)
CIF-error code |
0xA020 | CIF PROFIBUS® | Error in input data exchange with the CIF-card during SFC DPRD_DAT |
0xA021 | CIF PROFIBUS® | Timeout in output data exchange with the CIF-card during SFC DPWR_DAT |
0xA022 | CIF PROFIBUS® | Error in output data exchange with the CIF-card during SFC DPWR_DAT |
0xA023 | CIF PROFIBUS® | CIF-PROFIBUS®-card could not be detected |
0xA024 | CIF PROFIBUS® | CIF-PROFIBUS®-card could not be initialized |
0xA025 | MPI® | MPI®-telegram error |
0xA050 | CIF 30/50/60 | No CIF-driver installed |
0xA051 | CIF 30/50/60 | CIF-card could not be initialized |
0xA052 | CIF 30/50/60 | CIF-card not available |
0xA053 | CIF 30/50/60 | Timeout during cold start |
0xA054 | CIF 30/50/60 | Application could not be set to operational mode "READY" |
0xA055 | CIF 30/50/60 | Error in I/O-data exchange with the CIF-card during PII/PIQ update |
0xA056 | CIF 30/50/60 | Error in input data exchange with the CIF-card during T PI |
0xA057 | CIF 30/50/60 | Error in output data exchange with the CIF-card during T PQ |
0xA058 | CIF 30/50/60 | Error reading CIF-Task-mode |
0xA05A | CIF 30/50/60 | CIF-card could not be initialized |
0xA05B | CIF 30/50/60 | CIF-card could not be initialized |
0xA060 | CIF 30/50/60 | Error reading CIF-Task-mode |
0xA061 | CIF 30/50/60 | Error accessing the watchdog |
0xA062 | CIF 30/50/60 | CIF-driver not in operational mode "COM" |
0xA063 | CIF 30/50/60 | DevExchangeIO in ClearOutputs failed |
0xA064 | CIF 30/50/60 | Error reading CIF-driver status |
0xA065 | CIF 30/50/60 | Error reading CIF-driver status |
0xA069 | CIF 30/50/60 | Timeout in I/O-data exchange with the CIF-card during PII/PIQ update |
0xA070 | CIF 30/50/60 | Timeout in input data exchange with the CIF-card during L PI |
0xA071 | CIF 30/50/60 | Timeout in output data exchange with the CIF-card during T PQ |
0xA072 | CIF 30/50/60 | Timeout in input data exchange with the CIF-card during SFC DPRD_DAT |
0xA073 | CIF 30/50/60 | Error in input data exchange with the CIF-card during SFC DPWR_DAT |
0xA074 | CIF 30/50/60 | Timeout in input data exchange with the CIF-card during SFC DPRD_DAT |
0xA075 | CIF 30/50/60 | Error in output data exchange with the CIF-card |
0xA080 | CIF 30/50/60 | CIF-driver not ready |
0xA081 | CIF 30/50/60 | CIF-driver not in mode "RUN" |
0xA082 | CIF 30/50/60 | CIF-driver not in mode "COM" |
0xA090 | CIF30X | CIF-driver not ready |
0xA091 | CIF30X | CIF-driver not in mode "RUN" |
0xA092 | CIF30X | CIF-driver not in mode "COM" |
0xA100 | TwinCAT I/O | Port number from PLC43.INI, not available in TwinCAT task
Subsequent value is returned from TCatIoOpen |
0xA101 | TwinCAT I/O | Error in PLC43.INI
Periphery start < byte start |
0xA102 | TwinCAT I/O | PII/PIQ update during startup failed |
0xA103 | TwinCAT I/O | Error in PLC43.INI
Periphery < process image |
0xA104 | TwinCAT I/O | Timeout when connecting to TwinCAT driver
Subsequent value is returned from the last function |
0xA105 | TwinCAT I/O | TwinCAT driver not in RUN
Subsequent value is returned from the function TCatGetState() |
0xA106 | TwinCAT I/O | TwinCAT driver update ClearOutputs failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoOutputUpdate |
0xA107 | TwinCAT I/O | TwinCAT driver update PII failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoOutputUpdate |
0xA108 | TwinCAT I/O | TwinCAT driver update PIQ failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoOutputUpdate |
0xA109 | TwinCAT I/O | TwinCAT driver update LoadPI failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoInputUpdate |
0xA10A | TwinCAT I/O | TwinCAT driver update StorePY failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoOutputUpdate |
0xA10B | TwinCAT I/O | TwinCAT driver update while retriggering data failed (driver not in RUN anymore)
Subsequent value is returned from the TwinCAT function |
0xA10C | TwinCAT I/O | Saving the changed configuration during startup failed.
Subsequent value is returned from the function |
0xA10D | TwinCAT I/O | TCatIoInputUpdate reports 'Busy' during refreshing the inputs |
0xA10E | TwinCAT I/O | TCatIoInputUpdate reports 'Busy' during refreshing the inputs |
0xA10F | TwinCAT I/O | TwinCAT driver update PII failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoOutputUpdate |
0xA110 | TwinCAT I/O | TwinCAT driver update StorePQ failed (driver not in RUN anymore)
Subsequent value is returned from the function TCatIoOutputUpdate |
0xA111 | TwinCAT I/O | TCatIoGetInputPtr failed |
0xA112 | TwinCAT I/O | TCatIoGetOutputPtr failed |
0xA113 | TwinCAT I/O | ADS communication thread could not get local address and was closed. No ADS communication possible.
Next value is returned from the function __AdsGetLocalAddress,if value is 0, then __AdsPortOpen has failed |
0xA114 | TwinCAT I/O | AdsSyncReadReq in FDL communication failed |
0xA115 | TwinCAT I/O | AdsSyncWriteReq in FDL communication failed |
0xA116 | TwinCAT I/O | AdsSyncReadReq in FDL communication failed |
0xA117 | TwinCAT I/O | AdsSyncWriteReq in FDL communication failed |
0xA118 | TwinCAT I/O | AdsSyncWriteReq in FDL communication failed |
0xA119 | TwinCAT I/O | TCatIoOutputUpdate reports 'Busy' during refreshing the outputs |
0xA120 | Softnet PN IO | Softnet error code of function PNIO_set_mode followed by the
Softnet error code |
0xA121 | Softnet PN IO | Softnet error code of function PNIO_controller_open followed by
Index of the controller Softnet error code |
0xA122 | Softnet PN IO | Callback-error code for "mode change confirmation" followed by the
Softnet error code |
0xA123 | Softnet PN IO | Callback-error code for "device activate confirmation" followed by the
Softnet error code |
0xA124 | Softnet PN IO | Softnet error code of function PNIO_close followed by the
Softnet error code |
0xA126 | Softnet PN IO | Error in initialising of the Softnet PN IO driver |
0xA127 | Softnet PN IO | Softnet error code of function PNIO_set_mode operate followed by the
Softnet error code |
0xA128 | Softnet PN IO | Driver needs too much time to get into operate mode during initialization |
0xA140 | Addidata | Addidata error code
Subsequent value is returned from an ADDIPACK function |
0xA141 | I/O Port | No I/O Port access permitted by OS |
0xA148 | IBSPCI4 | Out of range error |
0xA149 | IBSPCI4 | openMXIDevice failed while opening the interbus board |
0xA14A | IBSPCI4 | closeMXIDevice failed while closing the interbus board |
0xA14B | IBSPCI4 | openDTIDevice failed while opening the interbus board |
0xA14C | IBSPCI4 | closeDTIDevice failed while closing the interbus board |
0xA150 | CIFX | Error in Profinet Diagnostics |
0xA151 | CIFX | Error in Profinet Diagnostics |
0xA152 | CIFX | Error on reset channel |
0xA153 | CIFX | Error on reset channel |
0xA154 | CIFX | Error on reset channel |
0xA155 | CIFX | Error in SFB 52 'RDREC' |
0xA156 | CIFX | Error in SFB 53 'WRREC' |
0xA161 | CIFX | Error on loading cifX driver |
0xA162 | CIFX | Error on sysdevice open |
0xA163 | CIFX | Error on channel open |
0xA164 | CIFX | Error on reset channel |
0xA165 | CIFX | Error on access host state |
0xA166 | CIFX | Error on access bus state |
0xA167 | CIFX | Error on reading input area PII |
0xA168 | CIFX | Error on writing output area PIQ |
0xA169 | CIFX | Error on reading periphery input area |
0xA16A | CIFX | Error on writing periphery output area |
0xA16B | CIFX | Error setting the watchdog |
0xA16C | CIFX | Error in xChannelIORead of SFC14 |
0xA16D | CIFX | Error in xChannelIORead of SFC15 |
0xA16F | CIFX | Error in xChannelInfo |
0xA170 | CIFX | Timeout starting the bus |
0xA171 | CIFX | Timeout starting the bus |
0xA172 | CIFX | Error in xSysdeviceInfo of SFC14 |
0xA173 | CIFX | Error in xSysdeviceInfo of SFC15 |
0xA174 | CIFX | Error initializing the Profibus board |
0xA175 | CIFX | Error deleting the Sycon.NET configuration. |
0xA176 | CIFX | Error configuring the card, make sure no .nxd file exists |
0xA177 | CIFX | Error configuring bus parameters |
0xA178 | CIFX | Error in Profibus Diagnostics |
0xA179 | CIFX | Error in Profibus Diagnostics |
0xA17A | CIFX | Error in Profibus Diagnostics |
0xA17B | CIFX | Error in Profibus Diagnostics |
0xA17C | CIFX | Error in Profibus Diagnostics |
0xA17D | CIFX | Error in Profibus Diagnostics |
0xA17E | CIFX | Error activating/deactivating slaves |
0xA17F | CIFX | Error in Profibus Diagnostics SFC13 |
0xA180 | CIFX | Error in SFC 59 'RD_REC' |
0xA181 | CIFX | Error in SFC 58 'WR_REC' |
0xA182 | CIFX | Error in SFB 52 'RDREC' |
0xA183 | CIFX | Error in SFB 53 'WRREC' |
0xA184 | CIFX | Error in Profibus Diagnostics |
0xA185 | CIFX | Error in xChannelExtendedStatusBlock |
0xA186 | CIFX | Error in xChannelExtendedStatusBlock |
0xA187 | CIFX | Error in xChannelExtendedStatusBlock |
0xA188 | CIFX | Error in xChannelExtendedStatusBlock |
0xA189 | CIFX | Error reconfiguring the card |
0xA18A | CIFX | CifX device driver < 0.946 and/or profibus firmware < 2.3.22.5 |
0xA190 | CIFX | Error analyzing the Profinet configuration |
0xA191 | CIFX | Error analyzing the Profinet configuration |
0xA192 | CIFX | Error retrieving the slave handles |
0xA193 | CIFX | Timeout during Profinet configuration occured |
0xA194 | CIFX | Error in configuration message of the Profinet configuration occured |