S7-SoftPLC:ADDI-DATA driver for S7-SoftPLC

From IBHsoftec Wiki English
Jump to: navigation, search

In order to activate the driver, the driver is included in the form dll0=addi_data.dll in the section [OEM].

The driver requires the section [addi_data], in which further parameters can be defined.

Name of parameter Default value Description
Read8FC 100 Number of FC Read8DigitalInputs
Read16FC 101 Number of FC Read16DigitalInputs
Read32FC 102 Number of FC Read32DigitalInputs
Set8FC 103 Number of FC Set8DigitalOutputs
Set16FC 104 Number of FC Set16DigitalOutputs
Set32FC 105 Number of FC Set32DigitalOutputs
InitAnaInpFC 106 Number of FC InitAnalogInput
RelAnaInpFC 107 Number of FC ReleaseAnalogInput
InitAnaOutFC 108 Number of FC InitAnalogOutput
ReadAnaInpFC 109 Number of FC ReadAnalogInput
WriteAnaOutFC 110 Number of FC WriteAnalogOutput
NoStop 0 0 = Driver is initialised at every PLC-START

1 = Driver is initialised once

It must be pointed out, that a unique number is assigned to every FC-block!

Example:

[OEM]
dll0=addi_data.dll
[addi_data]
Read8FC=100
Read16FC=101
Read32FC=102
Set8FC=103
Set16FC=104
Set32FC=105
InitAnaInpFC=106
RelAnaInpFC=107
InitAnaOutFC=108
ReadAnaInpFC=109
WriteAnaOutFC=110
NoStop=0