IBHNet:Technical Data IBH Link S7++/S7++ HS

From IBHsoftec Wiki English
Jump to: navigation, search

The IBH Link S7++ and the IBH Link S7++ HS have the same technical details except the following points:

  • The IBH Link S7++ HS has a rail mount.
  • The IBH Link S7++ HS has to be supplied with external 24V. The IBH Link S7++ can get the 24V from the MPI®/DP interface.
  • The "APL"-LED of the IBH Link S7++ HS is equal to the "COM"-LED of the IBH Link S7++.
  • The IBH Link S7++ HS has a rotary address switch to set the MPI®/DP-Address. A configured address in the range of 0-98 disables the address configuration with IBHNet. The MPI®/DP-Address 99 enables the the address configuration with IBHNet. The MPI®/DP-Address is taken from the rotary address switch only during a power cycle of the IBH Link S7++ HS.


Features:

  • Configuration via web browser
  • Configuration via NetPro
  • Windows®7 64 Bit support
  • STEP®7 64 Bit support
  • PROFIBUS diagnostics
  • Slave diagnostics
  • Drive configuration
  • Setting of the Slave Parameters via DPV1
  • Integration within the TIA portal
  • Routing via RFC1006
  • PLC - PLC communication
  • Process data access with other PLCs, Windows and Linux
  • 16 PC-connections at the same time
  • 32 MPI® / DP-connections at the same time
  • Automatic Baudrate detection
  • PG(PU)-connector (IBH Link S7++ only)
  • RJ45-Plug with autodetect integrated
  • Power supply from the MPI® / DP interface
  • Connection also to passive nodes with power supply via integrated 24V connector
  • DHCP
  • Diagnostic LEDs
  • Time synchronisation
  • Data set routing


Ethernet Interface

Ethernet pinout of the RJ45 female connector:

PlusRj45.jpg
Pin Signal Meaning
1 TD+ Receive Data +
2 TD- Receive Data -
3 RD+ Transmit Data +
4 n.c. not used
5 n.c. not used
6 RD- Transmit Data -
7 n.c. not used
8 n.c. not used


Ethernet Connection Data

Topology Star Topology
Medium 4 x 2 Twisted Pair copper cable Cat 3 (10 MBit/s), Cat 5 (100 MBit/s)
Length of cable 100m to the Device or to the next Hub and Switch respectively
Transmission rate 10 MBit/s / 100 MBit/s

 

Direct Connection Connection via Hub/Switch
PlusCross.jpg

 

Technical data

Ethernet Interface
Transmission rate 10 / 100 MBit/s
Interface max. 100 Base-TX potential free
Connector RJ45 female connector
PROFIBUS-Interface
Transmission rate RS485, max. 12 MBit/s


PlusAchtung.gif     Attention

The IBH Link S7++ only requires 24 VDC if not supplied by the PLC. Pay attention to polarity.


Meaning of LED-Signals

S7ppled2e.png

The COM-LED of the IBH Link S7++ and the IBH Link S7++ HS can be used for test functionality of the SIMATIC® Manager (PLC, Edit Ethernet Node).


Display Status IBH Link S7++

S7ppled3e.png