IBHNet:Technical Data IBH Link S7++/S7++ HS
From IBHsoftec Wiki English
The IBH Link S7++ and the IBH Link S7++ HS have the same technical details except the following points:
- The IBH Link S7++ HS has a rail mount.
- The IBH Link S7++ HS has to be supplied with external 24V. The IBH Link S7++ can get the 24V from the MPI®/DP interface.
- The "APL"-LED of the IBH Link S7++ HS is equal to the "COM"-LED of the IBH Link S7++.
- The IBH Link S7++ HS has a rotary address switch to set the MPI®/DP-Address. A configured address in the range of 0-98 disables the address configuration with IBHNet. The MPI®/DP-Address 99 enables the the address configuration with IBHNet. The MPI®/DP-Address is taken from the rotary address switch only during a power cycle of the IBH Link S7++ HS.
Contents
Features:
- Configuration via web browser
- Configuration via NetPro
- Windows®7 64 Bit support
- STEP®7 64 Bit support
- PROFIBUS diagnostics
- Slave diagnostics
- Drive configuration
- Setting of the Slave Parameters via DPV1
- Integration within the TIA portal
- Routing via RFC1006
- PLC - PLC communication
- Process data access with other PLCs, Windows and Linux
- 16 PC-connections at the same time
- 32 MPI® / DP-connections at the same time
- Automatic Baudrate detection
- PG(PU)-connector (IBH Link S7++ only)
- RJ45-Plug with autodetect integrated
- Power supply from the MPI® / DP interface
- Connection also to passive nodes with power supply via integrated 24V connector
- DHCP
- Diagnostic LEDs
- Time synchronisation
- Data set routing
Ethernet Interface
Ethernet pinout of the RJ45 female connector:
Pin | Signal | Meaning |
---|---|---|
1 | TD+ | Receive Data + |
2 | TD- | Receive Data - |
3 | RD+ | Transmit Data + |
4 | n.c. | not used |
5 | n.c. | not used |
6 | RD- | Transmit Data - |
7 | n.c. | not used |
8 | n.c. | not used |
Ethernet Connection Data
Topology | Star Topology |
Medium | 4 x 2 Twisted Pair copper cable Cat 3 (10 MBit/s), Cat 5 (100 MBit/s) |
Length of cable | 100m to the Device or to the next Hub and Switch respectively |
Transmission rate | 10 MBit/s / 100 MBit/s |
Direct Connection | Connection via Hub/Switch |
Technical data
Ethernet Interface | |
---|---|
Transmission rate | 10 / 100 MBit/s |
Interface | max. 100 Base-TX potential free |
Connector | RJ45 female connector |
PROFIBUS-Interface | |
Transmission rate | RS485, max. 12 MBit/s |
The IBH Link S7++ only requires 24 VDC if not supplied by the PLC. Pay attention to polarity.
Meaning of LED-Signals
The COM-LED of the IBH Link S7++ and the IBH Link S7++ HS can be used for test functionality of the SIMATIC® Manager (PLC, Edit Ethernet Node).