IBHNet:Technical Data IBH Link S5++
From IBHsoftec Wiki English
Features
- S5 PU Connections
- Fetch/Write Connections
- RFC1006 for S7 HMI devices
- Diagnostic LEDs
- RJ45
- Power supply directly from the PLC
- Passive PLCs also possible with integrated 24V connector
Interfaces
| Interface | Type | Factory settings |
|---|---|---|
| Ethernet | 10/100MBPs, Auto Negotiation | 192.168.1.13 |
| USB-Device | Fullspeed (12 MBits/s), Ethernet Emulation, Powered by Device | 192.168.167.12 |
| UART | 20mA (TTY / Current Loop) | 9600 Baud |
| Power supply | 3.81mm, 2 Polig |
D-SUB15
| PIN | Signal | Meaning |
|---|---|---|
| 1 | GND | |
| 2 | TXD-Out | Open-Collector Out |
| 3 | N.C. | N.C. = not connected |
| 4 | Ext. | 5V-In external supply |
| 5 | N.C. | |
| 6 | +3.3V | |
| 7 | RXD-In | |
| 8 | N.C | |
| 9 | 3.3V-R | Connected with 3.3V over resistor 165 Ohm |
| 10 | GND | |
| 11 | N.C. | |
| 12 | N.C. | |
| 13 | N.C. | |
| 14 | N.C. | |
| 15 | N.C. |
LED-Meaning
| LED | State | Meaning |
|---|---|---|
| LINK / ACTIVITY | Flashing | Activity Ethernet |
| SPEED | On | 100MBps Ethernet |
| FDX / COLL | On | Full Duplex Ethernet |
| Ready | On | Device Ready |
| Flashing | Boot Process | |
| Busy / Error | On | Error |
| Flashing | Boot Process |
The IBH Link S5++ only requires 24 VDC if not supplied by the PLC. The external terminal needs to be supplied with 0V, the internal terminal with 24V DC. Pay attention to polarity.
Electrical data
| Parameter | Min | Typ | Max | Unit |
|---|---|---|---|---|
| Power supply | 8 | 12 | 30 | V (DC) |
| Power consumption | 1 | W | ||
| Current (USB) | <20 | mA | ||
| Operating temparature | 0 | 60 | °C | |
| Storage temperature | -25 | 75 | °C | |
| Protection | IP20 |
Mechanical data
| Parameter | Min | Typ | Max | Unit |
|---|---|---|---|---|
| Length | 58 | mm | ||
| Width | 42 | mm | ||
| Height | 18 | mm | ||
| Weight | 43 | g |