IBHLink S5++:PLC-PLC communication
From IBHsoftec Wiki English
Data exchange between a S7 controller S7-300 / S7-400 / S7-1200 / S7-1500 and a SIMATIC S5 PLC via IBH Link S5++
Requirements:
- IBH Link S5++
- CPU with Ethernet onboard or Ethernet CP. The Interface must support S7 connections. It can be checked within the hardware
properties: S7 connection active (Server means passive).
For the connection to an IBH Link S5++, no dummy CPU needs to be configured within NetPro. It is enough to create an unspecified S7 connection via Ethernet. In this case, the partner IP address is the IP address of the IBH Link S5++. Within the Address Details for the Partner Rack = 0 and Slot = 2 must be selected. For communication, the blocks PUT/GET are chosen - SFB14/15.