Difference between revisions of "S7-SoftPLC:Using the IBH S7-SoftPLC with Intouch via RFC1006"

From IBHsoftec Wiki English
Jump to: navigation, search
(Created page with "In order to use the RFC1006 function of the ''IBH S7-SoftPLC'' with Intouch, please follow the description step by step. -Start the System Management Console: <Start->...")
 
 
Line 5: Line 5:
 
&lt;Start-&gt;Programs-&gt;Wonderware-&gt;System Management Console&gt;
 
&lt;Start-&gt;Programs-&gt;Wonderware-&gt;System Management Console&gt;
  
[[Image:DAserver1.png|frame|none]]
+
[[Image:DAserver1_eng.png|frame|none]]
  
 
- As &lt;Network Address&gt; enter the IP Address of the ''IBH S7-SoftPLC''.
 
- As &lt;Network Address&gt; enter the IP Address of the ''IBH S7-SoftPLC''.
Line 17: Line 17:
 
- Then the Device Group needs to be entered (via this name the WW Client accesses the ''IBH S7-SoftPLC''.
 
- Then the Device Group needs to be entered (via this name the WW Client accesses the ''IBH S7-SoftPLC''.
  
[[Image:DAserver2.png|frame|none]]
+
[[Image:DAserver2_eng.png|frame|none]]
  
 
- Then the Wonderware Client needs to be configured:
 
- Then the Wonderware Client needs to be configured:
Line 23: Line 23:
 
&lt;Start -&gt; Programs -&gt; Wonderware Factory Suite -&gt; Common-&gt; WWClient&gt;.
 
&lt;Start -&gt; Programs -&gt; Wonderware Factory Suite -&gt; Common-&gt; WWClient&gt;.
  
[[Image:DAserver3.png|frame|none]]
+
[[Image:DAserver3_eng.png|frame|none]]
  
[[Image:DAserver4.png|frame|none]]
+
[[Image:DAserver4_eng.png|frame|none]]
  
 
- The Field &lt;Node&gt; needs to be empty, as &lt;Topic&gt; the Device Groups Name will be used.
 
- The Field &lt;Node&gt; needs to be empty, as &lt;Topic&gt; the Device Groups Name will be used.
Line 31: Line 31:
 
- After successful configuration, the desired items can be entered and be activated via the Button &lt;AdviseEX&gt;:
 
- After successful configuration, the desired items can be entered and be activated via the Button &lt;AdviseEX&gt;:
  
[[Image:DAserver5.png|frame|none]]
+
[[Image:DAserver5_eng.png|frame|none]]
  
 
- With the activated SIDirect DA-Server, the configured items should appear in the Wonderware Client Connection Window with their current value:
 
- With the activated SIDirect DA-Server, the configured items should appear in the Wonderware Client Connection Window with their current value:
  
[[Image:DAserver6.png|frame|none]]
+
[[Image:DAserver6_eng.png|frame|none]]

Latest revision as of 12:18, 19 December 2012

In order to use the RFC1006 function of the IBH S7-SoftPLC with Intouch, please follow the description step by step.

-Start the System Management Console:

<Start->Programs->Wonderware->System Management Console>

DAserver1 eng.png

- As <Network Address> enter the IP Address of the IBH S7-SoftPLC.

- <Remote Rack No.> = 0 Rack Address of the PLC

<Remote Slot No.> = 2 MPI Address of the PLC

<Connection Resource> = 2.

- Then the Device Group needs to be entered (via this name the WW Client accesses the IBH S7-SoftPLC.

DAserver2 eng.png

- Then the Wonderware Client needs to be configured:

<Start -> Programs -> Wonderware Factory Suite -> Common-> WWClient>.

DAserver3 eng.png
DAserver4 eng.png

- The Field <Node> needs to be empty, as <Topic> the Device Groups Name will be used.

- After successful configuration, the desired items can be entered and be activated via the Button <AdviseEX>:

DAserver5 eng.png

- With the activated SIDirect DA-Server, the configured items should appear in the Wonderware Client Connection Window with their current value:

DAserver6 eng.png