== Establishing a connection to a SIMATIC® S5 PLC via SINEC L2/PROFIBUS using a modern PC ==
+
== Establishing a connection to a SIMATIC S5 PLC via SINEC L2/PROFIBUS using a modern PC ==
  
Becasue of IT security only PCs with current operating systems including latest OS and virus scanner updates are allowed to use in corporate networks. So the usagee of old PCs that allowed a programming via SINEC L2/PROFIBUS is no longer possible.
+
Because of IT security issues, only PCs with current operating systems including latest OS security updates and virus scanner updates are allowed to be used in corporate networks. The usage of old PCs, that allowed programming via SINEC L2/PROFIBUS is often no longer permitted and therefore no more possible.
  
Within environment with old SIMATIC® S5 PLC often SINEC L2/PROFIBUS is used to communicate with the control level or scada via Ethernet.  
+
In many production environments with old SIMATIC S5 PLCs, often SINEC L2/PROFIBUS is used to communicate with the control level or scada via Ethernet. Since it is also possible to program the PLC via SINEC L2/PROFIBUS, this task must now be performed with modern PCs.
  
Soft and Hardware requiremets:
+
Soft and Hardware requirements:
  
* A PC with a usaul network card.
+
* A PC with a standard ethernet network card.
  
 
* Our '''[http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBHLink S7++]'''.
 
* Our '''[http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBHLink S7++]'''.
Line 15: Line 15:
 
* '''[http://www.ibhsoftec.com/S5W-Eng S5 for Windows®]'''
 
* '''[http://www.ibhsoftec.com/S5W-Eng S5 for Windows®]'''
  
First, an implementation of the H1 Ethernet network to modern twisted pair cabling with standard RJ45 connectors must be done. Therefore the Ethernet to PROFIBUS Gateway '''IBH Link S7++''' is used.
+
First, a conversion of the SINEC L2/PROFIBUS network to modern twisted pair cabling with standard RJ45 connectors must be done. To do the physical media conversion, the Ethernet to PROFIBUS Gateway '''IBH Link S7++''' is used.
  
Bevor der IBH Link S7++ auf den PROFIBUS augesteckt wird, muss man im '''IBH Link S7++''' die Parameter des PROFIBUS einstellen. Die zu verwendenden Parameter müssen aus der Projektierung des verwendeten Kommunikationsprozessors abgelesen werden. Bei einer S5-95U mit PROFIBUS finden sich die Parameter im DB1, bei einem CP5431 kann dies mit dem COM-Paket COM5430 aus dem CP ausgelesen werden.
+
Before plugging the IBH Link S7++ on PROFIBUS, the PROFIBUS parameters must be set up correctly. The actual settings of the parameters must be read out from the configuration of the used communication processor. For a S5 95U with PROFIBUS, the parameters can be found within the DB1. If a CP5431 is used, the COM package COM5430 delivers the required information.
  
Die Parameter können nun mit einem normalen Internet Broswer im '''IBH Link S7++''' eingestellt werden. Optional kann die Einstellung der Parameter auch über den mitgelieferten IBHNet Treiber erfolgen.
+
The parameters can be set in the '''IBH Link S7++''' with a standard webbrowser. Likewise, the bus parameters can also be configured with the IBHNet configuration tool.
  
'''IBH Link S7++ on the PROFIBUS connector of a S5-95U'''
+
'''IBH Link S7++ on the PROFIBUS connector of a S5 95U'''
  
 
[[Image:IBHLink-S7-95u-profibus.jpg|400px]]
 
[[Image:IBHLink-S7-95u-profibus.jpg|400px]]
Line 29: Line 29:
 
[[Image:IBHLink-S7-CP5431-profibus.jpg|400px]]
 
[[Image:IBHLink-S7-CP5431-profibus.jpg|400px]]
  
Zusätzlich muss der '''IBH Link S7++''' bei Verwendung auf S5-Steuerungen extern mit 24V Betriebsspannung versorgt werden.
+
The external 24 V power supply for the '''IBH Link S7++''' must be connected, when using it with a S5 PLC.  
  
Within the Onlinetree seclet '''<Network>''' and choose '''<New S5-SINEC-L2 Station..>''' using the right mosue button:
+
The Profibus CP must be connected to the PG port of the CPU via the so called '''monkey swing'''. '''[https://download.ibhsoftec.com/Customer/S5_Monkey_Swing.pdf Pin Out ]'''
 +
 
 +
Within the online tree select '''<Network>''' and choose '''<New S5-SINEC-L2 Station..>''' using the right mosue button:
  
 
'''Setup of an SINEC-L2 connection'''
 
'''Setup of an SINEC-L2 connection'''
Line 37: Line 39:
 
[[Image:L2 Station eng.png‎]]
 
[[Image:L2 Station eng.png‎]]
  
This allows the porgramming via SINEC L2/PROFIBUS uisng the '''IBH Link S7++'''.
+
This allows the programming via SINEC L2/PROFIBUS using the '''IBH Link S7++'''.
 +
Details about the setup of the SINEC-L2 connection can be found at:
 +
* [[IBHLink S7++:SIMATIC® S5 for Windows®|Access to a SIMATIC® S5 with ''S5 for Windows®'' via SINEC L2]]

Latest revision as of 11:12, 12 January 2022

Establishing a connection to a SIMATIC S5 PLC via SINEC L2/PROFIBUS using a modern PC

Because of IT security issues, only PCs with current operating systems including latest OS security updates and virus scanner updates are allowed to be used in corporate networks. The usage of old PCs, that allowed programming via SINEC L2/PROFIBUS is often no longer permitted and therefore no more possible.

In many production environments with old SIMATIC S5 PLCs, often SINEC L2/PROFIBUS is used to communicate with the control level or scada via Ethernet. Since it is also possible to program the PLC via SINEC L2/PROFIBUS, this task must now be performed with modern PCs.

Soft and Hardware requirements:

  • A PC with a standard ethernet network card.
  • Windows XP, VISTA, 7 or 8 (32-Bit or 64-Bit).

First, a conversion of the SINEC L2/PROFIBUS network to modern twisted pair cabling with standard RJ45 connectors must be done. To do the physical media conversion, the Ethernet to PROFIBUS Gateway IBH Link S7++ is used.

Before plugging the IBH Link S7++ on PROFIBUS, the PROFIBUS parameters must be set up correctly. The actual settings of the parameters must be read out from the configuration of the used communication processor. For a S5 95U with PROFIBUS, the parameters can be found within the DB1. If a CP5431 is used, the COM package COM5430 delivers the required information.

The parameters can be set in the IBH Link S7++ with a standard webbrowser. Likewise, the bus parameters can also be configured with the IBHNet configuration tool.

IBH Link S7++ on the PROFIBUS connector of a S5 95U

IBHLink-S7-95u-profibus.jpg

IBH Link S7++ on the PROFIBUS connector of a CP5431

IBHLink-S7-CP5431-profibus.jpg

The external 24 V power supply for the IBH Link S7++ must be connected, when using it with a S5 PLC.

The Profibus CP must be connected to the PG port of the CPU via the so called monkey swing. Pin Out

Within the online tree select <Network> and choose <New S5-SINEC-L2 Station..> using the right mosue button:

Setup of an SINEC-L2 connection

L2 Station eng.png

This allows the programming via SINEC L2/PROFIBUS using the IBH Link S7++. Details about the setup of the SINEC-L2 connection can be found at: