Difference between revisions of "S/-SoftPLC:Configuration TwinCAT I/O with PLC43.INI"
From IBHsoftec Wiki English
|
|
Line 1: |
Line 1: |
− | To activate the driver it must be included in the section [OEM]. The required entry is for example:
| |
| | | |
− | [OEM]
| |
− | dll0=TwinCatIO.dll
| |
− |
| |
− | In the PLC43.INI the following parameters must be defined in the section [TwinCatIO].
| |
− |
| |
− | {| class="wikitable"
| |
− | |-
| |
− | ! Parameter !! Default value !! Description
| |
− | |-
| |
− | |style="width:15em"| PortNumber ||style="width:10em"| 301 || Set port of I/O-task in TwinCAT System Manager.
| |
− | If PortNumber=0 the exchange of process images is disabled. Access is possible via SFC/FC only.
| |
− | If the port number does not match the TwinCAT I/O task, S7-SoftPLC switches to STOP.
| |
− | |-
| |
− | | SFC14 || 1 || Show SFC 14
| |
− | |-
| |
− | | SFC15 || 1 || Show SFC 15
| |
− | |-
| |
− | | ControlSFC || 1000 || Number of Control SFC
| |
− | |-
| |
− | | NoStop || 0 || Do not stop fieldbus at PLC Stop
| |
− | |-
| |
− | | TypeFC || 0 || Show SFCs as FCs
| |
− | |-
| |
− | | FB_CxGetDeviceIdentification || 1001 || Number of GetDeviceIdentification FB
| |
− | |-
| |
− | | FB_AdsRead || 1002 || Number of AdsRead FB
| |
− | |-
| |
− | | FB_AdsWrite || 1003 || Number of AdsWrite FB
| |
− | |}
| |
− |
| |
− | ==== Example: ====
| |
− |
| |
− | [OEM]
| |
− | dll0=TwinCatIO.dll
| |
− |
| |
− | [TWINCATIO]
| |
− | PortNumber=301
| |
− | SFC14=1
| |
− | SFC15=1
| |
− | ControlSFC=1000
| |
− | NoStop=0
| |
− | TypeFC=0
| |
− | FB_CxGetDeviceIdentification=1001
| |
− | FB_AdsRead=1002
| |
− | FB_AdsWrite=1003
| |
Latest revision as of 09:19, 17 January 2013