Line 5: Line 5:
  
 
* Add a '''OPC Node''' via '''<Add OPC Object>''' with the name '''IBH''':
 
* Add a '''OPC Node''' via '''<Add OPC Object>''' with the name '''IBH''':
[[Image:FS gateway Add OPC Object.png|378px]]
+
:[[Image:FS gateway Add OPC Object.png|378px]]
  
[[Image:FS gateway OPC Objekt.png|807px]]
+
:[[Image:FS gateway OPC Objekt.png|807px]]
 
:As '''<Server Node>''' enter the IP Address of the PC , where the IBH OPC Server is running:<br />
 
:As '''<Server Node>''' enter the IP Address of the PC , where the IBH OPC Server is running:<br />
 
:As '''<Server Name>''' choose the IBH OPC Server:<br />
 
:As '''<Server Name>''' choose the IBH OPC Server:<br />
Line 13: Line 13:
  
 
* Add a '''OPC Group''' with the name '''OPC_Server''':
 
* Add a '''OPC Group''' with the name '''OPC_Server''':
[[Image:FS gateway OPC Group Object eng.png|847px]]
+
:[[Image:FS gateway OPC Group Object eng.png|847px]]
 
:Within the filed '''<OPC Item ID Prefix>''' the name of the PLC can be entered, which was created within IBH OPC Editor f.e. '''PLC1''' followed by a dot.
 
:Within the filed '''<OPC Item ID Prefix>''' the name of the PLC can be entered, which was created within IBH OPC Editor f.e. '''PLC1''' followed by a dot.
:Within the '''<Item>''' creation the notation ''<Access-path>''' is not necessary.<br />
+
:[[Image:IBH OPC PLC properties.png|295px]]
 +
:So the notation '''<Access-path>''' within the later '''<Item>''' creation can be omitted.<br />
  
  
 
* Start the '''Intouch WindowMaker''' and create a new Acess name f.e. IBH_OPC :
 
* Start the '''Intouch WindowMaker''' and create a new Acess name f.e. IBH_OPC :
[[Image:FS gateway Zugriffsname.png|394px]]
+
:[[Image:FS gateway Access name.png|408px]]
 
:As '''<Node name>''' enter the IP Address of the PC , where the IBH OPC Server is running:<br />
 
:As '''<Node name>''' enter the IP Address of the PC , where the IBH OPC Server is running:<br />
 
:As '''<Application name>''' enter '''FSGateway'''.<br />
 
:As '''<Application name>''' enter '''FSGateway'''.<br />
Line 25: Line 26:
  
  
* Now the Variables can be created:
+
* Now the Tagnamess can be created:
[[Image:FS gateway Variable.png|600px]]
+
:[[Image:FS gateway Tagname.png|600px]]
 
:Select the newly created '''Access Name''': IBH_OPC.  
 
:Select the newly created '''Access Name''': IBH_OPC.  
:The entry '''<Item>''' consists of :
+
:The entry '''<Item>''' consists of:
'''<Access-Path>.<Item Name>'''.  
+
:'''<Access-Path>.<Item Name>'''.  
 
:The '''<Access-Path>''' represents the name of the <PLC>, which has been created in the IBH OPC Editor.
 
:The '''<Access-Path>''' represents the name of the <PLC>, which has been created in the IBH OPC Editor.
 
:The '''<Access-Path>''' is not necessary in our sample, because it is aready defined within '''<OPC Item ID Prefix>''' .
 
:The '''<Access-Path>''' is not necessary in our sample, because it is aready defined within '''<OPC Item ID Prefix>''' .
Line 38: Line 39:
  
 
* The configuration is now completed and the variables can be used:
 
* The configuration is now completed and the variables can be used:
[[Image:FS gateway Leuchtmelder.png|552px]]
+
:[[Image:FS gateway Light Wizard.png|554px]]

Latest revision as of 10:12, 30 October 2012

Create Variables with Intouch FS Gateway

To create Variables with Intouch FS Gateway with Intouch, please follow the description step by step.

  • Start the ArchestrA System Management Console
Start ⇒ Programme ⇒ Wonderware ⇒ System Management Console
  • Add a OPC Node via <Add OPC Object> with the name IBH:
FS gateway Add OPC Object.png
FS gateway OPC Objekt.png
As <Server Node> enter the IP Address of the PC , where the IBH OPC Server is running:
As <Server Name> choose the IBH OPC Server:


  • Add a OPC Group with the name OPC_Server:
FS gateway OPC Group Object eng.png
Within the filed <OPC Item ID Prefix> the name of the PLC can be entered, which was created within IBH OPC Editor f.e. PLC1 followed by a dot.
IBH OPC PLC properties.png
So the notation <Access-path> within the later <Item> creation can be omitted.


  • Start the Intouch WindowMaker and create a new Acess name f.e. IBH_OPC :
FS gateway Access name.png
As <Node name> enter the IP Address of the PC , where the IBH OPC Server is running:
As <Application name> enter FSGateway.
The <Topic-Name> is the combination of Node name IBH and OPC Group name OPC_Server.


  • Now the Tagnamess can be created:
FS gateway Tagname.png
Select the newly created Access Name: IBH_OPC.
The entry <Item> consists of:
<Access-Path>.<Item Name>.
The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor.
The <Access-Path> is not necessary in our sample, because it is aready defined within <OPC Item ID Prefix> .
To access the variables which are already defined within the IBH OPC Editor the correct syntax is:
Generic.<Variable Name>


  • The configuration is now completed and the variables can be used:
FS gateway Light Wizard.png