Difference between revisions of "IBH Link UA:Loading multible projects into the IBH Link UA"
(Created page with "== Using multiple STEP7 and / or TIA projects in parallel == It may happen that not all controllers can be integrated in a common project. Therefore, several individual proje...") |
(→Using multiple STEP7 and / or TIA projects in parallel) |
||
Line 1: | Line 1: | ||
== Using multiple STEP7 and / or TIA projects in parallel == | == Using multiple STEP7 and / or TIA projects in parallel == | ||
− | It may happen that not all controllers can be integrated in a common project. Therefore, several individual projects can be loaded into the IBH Link UA . Each project must be loaded in a separate slot for this purpose | + | It may happen that not all controllers can be integrated in a common project. Therefore, several individual projects can be loaded into the IBH Link UA . Each project must be loaded in a separate slot for this purpose. |
The IBH Link UA can handle up to 31 STEP7 and / or TIA projects in parallel. | The IBH Link UA can handle up to 31 STEP7 and / or TIA projects in parallel. |
Latest revision as of 18:12, 9 March 2015
Contents
Using multiple STEP7 and / or TIA projects in parallel
It may happen that not all controllers can be integrated in a common project. Therefore, several individual projects can be loaded into the IBH Link UA . Each project must be loaded in a separate slot for this purpose.
The IBH Link UA can handle up to 31 STEP7 and / or TIA projects in parallel.
Configuration with the TIA Portal
The Ethernet CP must be placed on slot 2 (within TIA Portal named Index)
Attention!
The configuration of the Ethernet CP MUST be identical in ALL individual projects
For the OPC Server the slots 1 and 3-32 can be used:
The slots represent each individual projects:
Configuration with STEP7
The Ethernet CP must be placed on slot 2
Attention!
The configuration of the Ethernet CP MUST be identical in ALL individual projects
For the OPC Server the slots 1 and 3-32 can be used:
The slots represent each individual projects:
OPC Slots
The sample shows a TIA project from a S7-1200 and a STEP7 project from a S7-315-2 DP:
Using the web interface selectd or all slots can be deleted.
Forbid project download with STEP®7 or TIA Portal
An unintentional overwriting of the configuration can be prevented: