IBHNet:RFC1006 Communication IBH Link S7++/S7++HS

From IBHsoftec Wiki English
Jump to navigation Jump to search
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.


PC-based visualization systems can be coupled by the IBH Link S7++ / S7++ HS to an S7 PLC without the IBHNet driver in order to read and write data.


The IBH Link S7 / S7 Plus needs an additional tool for the RFC1006 communication. For details see chapter "RFC1006 Communication IBH Link S7 / S7 Plus".


RFC1006 uses a rack and a slot number for addressing. These are directly converted to the MPI address. In order to access MPI address 2 you need to use the value 0 for the rack number and 2 for the slot number on the side of RFC1006, for precise assignment see the table below. Some visualization software needs the TSAP. The assignment is listed in the following table:

MPI Rack Slot TSAP
0 0 0 0200
1 0 1 0201
2 0 2 0202
... ... ... ...
31 0 31 021F
32 1 0 0220
33 1 1 0221
... ... ... ...
63 1 31 023F
64 2 0 0240
65 2 1 0241
... ... ... ...
95 2 31 025F
96 3 0 0260
97 3 1 0261
... ... ... ...
126 3 30 027E