It is possible to realize a connection from a PC with Elipse Scada to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.
+
It is possible to realize a connection from a PC with '''Elipse SCADA''' to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.
  
 
==Example==
 
==Example==
In the following example a configuration with Elipse Scada is shown.
+
In the following example a configuration with '''Elipse SCADA''' is shown.
The HMI station ist connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.
+
The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.
  
 
The following addresses were chosen in the example:
 
The following addresses were chosen in the example:
Line 29: Line 29:
 
Configuration:
 
Configuration:
  
The ethernet communication driver for S7 300/400 must be selected in WinCC flexible, since only this driver allows the selection of an extension slot on the PLC side. This setting is necessary for the selection of the PPI address to use for the connection.
+
The ethernet communication driver for S7-300/400 named '''MProt.dll''' must be selected witin the Application Organizer:
 +
[[Image:Elipse_driver.png|600px]]
  
[[Image:S7-200_WinCCflex.png|600px]]
+
Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address>
 +
[[Image:Elipse_driver_settings.png|456px]]<br />
  
If you are using the WinCC flexible Runtime, please check that in the settings of the PG/PC Interface the correct driver ''TCP/IP'' for the Access Point ''S7ONLINE'' is chosen.
 
  
[[Image:PGPC_Setting_TCPIP.png|400px]]
+
Enter the IP Address of the IBH LinkS7 ++ and choose port 102:<br />
  
The configuration of the connection is now completed and you can continue with defining your Tags.
+
[[Image:Elipse_driver_settings_ethernet.png|456px]]
 +
 
 +
Now the '''N''' an '''P''' Parameters must be set. The description you'll find within the helpfile '''<mprot_us.chm>'''<br />
 +
In the sample DB1.DB0 is chosen:<br />
 +
 
 +
[[Image:Elipse_P_paramter.png|597px]]
 +
[[Image:Elipse_N_paramter.png|597px]]
 +
 
 +
The configuration is now completed and the Tags can be used:<br />
 +
[[Image:Elipse_tags.png|397px]]

Latest revision as of 14:01, 4 June 2012

It is possible to realize a connection from a PC with Elipse SCADA to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.

Example

In the following example a configuration with Elipse SCADA is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S7++ 192.168.10.125

PPI addresses:

Station Address
IBHLink S7++ 17
S7-300/S7-400 station 2

Configuration:

The ethernet communication driver for S7-300/400 named MProt.dll must be selected witin the Application Organizer: Elipse driver.png

Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address> Elipse driver settings.png


Enter the IP Address of the IBH LinkS7 ++ and choose port 102:

Elipse driver settings ethernet.png

Now the N an P Parameters must be set. The description you'll find within the helpfile <mprot_us.chm>
In the sample DB1.DB0 is chosen:

Elipse P paramter.png Elipse N paramter.png

The configuration is now completed and the Tags can be used:
Elipse tags.png