S7-PCI315 instruction set
The S7-PCI315 PLC has the complete instruction set of the SIMATIC® S7-315 PLC.
Bit logic instructions
Instruction |
Operand |
Description
|
A |
|
AND with a scan to "1"
|
AN |
|
AND with a scan to "0"
|
O |
|
OR with scan to "1"
|
ON |
|
OR with scan to "0"
|
X |
|
Exclusive-OR with a scan to "1"
|
XN |
|
Exclusive-OR with a scan to "0"
|
|
I |
of an input
|
|
Q |
of an output
|
|
M |
of a memory flag
|
|
L |
of a local data bit
|
|
T |
of a timer
|
|
C |
of a counter
|
|
DBX |
of a data bit
|
|
DIX |
of an instance data bit
|
==0 |
|
result equal zero
|
<>0 |
|
result unequal zero
|
>0 |
|
result greater than zero
|
>=0 |
|
result greater or equal zero
|
<0 |
|
result less than zero
|
<=0 |
|
result less or equal zero
|
UO |
|
invalid result
|
OV |
|
overflow
|
OS |
|
overflow (saved)
|
BR |
|
binary result
|
Other boolean logic instructions
Operation |
Operand |
Description
|
A( |
|
AND left parenthesis
|
AN( |
|
AND NOT left parenthesis
|
O( |
|
OR left parenthesis
|
ON( |
|
OR NOT left parenthesis
|
X( |
|
Exclusive OR left parenthesis
|
XN( |
|
Exclusive OR NOT left parenthesis
|
) |
|
Right parenthesis
|
O |
|
OR-ing AND operations
|
NOT |
|
Negate RLO
|
SET |
|
Set RLO to "1"
|
CLR |
|
Set RLO to "0"
|
SAVE |
|
Save RLO to the BR bit
|
Operation |
Operand |
Description
|
= |
|
Assign value of RLO
|
S |
|
Set
|
R |
|
Reset
|
FP |
|
Positive edge detection
|
FN |
|
Negative edge detection
|
|
I |
of an input bit
|
|
Q |
of an output bit
|
|
M |
of a flag memory bit
|
|
L |
of a local data bit
|
|
DBX |
of a data bit
|
|
DIX |
of an instance data bit
|
Master Control Relay
Operation |
Operand |
Description
|
MCRA |
|
Activate MCR
|
MCRD |
|
Deactivate MCR
|
MCR( |
|
Open MCR zone
|
)MCR |
|
Close MCR zone
|
Load / Transfer instructions
Operation |
Operand |
Description
|
L |
|
Load operand
|
T |
|
Transfer operand
|
|
IB |
Input byte
|
|
IW |
Input word
|
|
ID |
Input double word
|
|
QB |
Output byte
|
|
QW |
Output word
|
|
QD |
Output double word
|
|
MB |
Memory byte
|
|
MW |
Memory word
|
|
MD |
Memory double word
|
|
LB |
Local data byte
|
|
LW |
Local data word
|
|
LD |
Local data double word
|
|
DBB |
Data block byte
|
|
DBW |
Data block word
|
|
DBD |
Data block double word
|
|
DIB |
Instance data block byte
|
|
DIW |
Instance data block word
|
|
DID |
Instance data block double word
|
|
STW |
Status word
|
L |
Const |
Load constant value
|
L |
#Pointer |
Load pointer
|
L |
T |
Timer
|
LC |
T |
Timer (BCD coded)
|
L |
C |
Counter
|
LC |
C |
Counter (BCD coded)
|
L |
DBNO |
Data block number
|
L |
DBLG |
Data block length
|
L |
DINO |
Instance data block number
|
L |
DILG |
Instance data block length
|
Peripheral access instructions
Operation |
Operand |
Description
|
L |
PIB |
Load peripheral input byte
|
L |
PIW |
Load peripheral input word
|
L |
PID |
Load peripheral input double word
|
T |
PQB |
Transfer peripheral output byte
|
T |
PQW |
Transfer peripheral output word
|
T |
PQD |
Transfer peripheral output double word
|
Accumulator instructions
Operation |
Operand |
Description
|
PUSH |
|
Push accumulators upwards
|
POP |
|
Push accumulators downwards
|
ENT |
|
Push accumulators (without A1) A2->A3, A3->A4
|
LEAVE |
|
Push accumulators (without A1) A4->A3, A3->A2
|
TAK |
|
Change ACCU1 with ACCU2
|
CAW |
|
Change ACCU1 bytes 0 and 1
|
CAD |
|
Change ACCU1 bytes 0 and 3, 1 and 2
|
Shift and rotating instructions
Operation |
Operand |
Description
|
SLW |
|
Shift ACCU1-L left (word shift)
|
SLD |
|
Shift ACCU1 left (double word shift)
|
SRW |
|
Shift ACCU1-L right (word shift)
|
SRD |
|
Shift ACCU1 right (double word shift)
|
SSI |
|
Shift ACCU1-L right (word shift with sign)
|
SSD |
|
Shift ACCU1 right (double word shift with sign)
|
RLD |
|
Rotate ACCU1 left (double word)
|
RLDA |
|
Rotate ACCU1 left through CC1
|
RRDA |
|
Rotate ACCU1 right through CC1
|
RRD |
|
Rotate ACCU1 right (double word)
|
|
Const |
Number of places to shift/rotate
|
|
|
Number of places to shift/rotate located in ACCU2
|
Timer instructions
Operation |
Operand |
Description
|
SP |
T |
Start as impulse
|
SE |
T |
Start as extended impulse
|
SD |
T |
Start as ON-delay
|
SS |
T |
Start as saving ON-delay
|
SF |
T |
Start as OFF-delay
|
R |
T |
Reset timer
|
FR |
T |
Enable timer
|
Counter instructions
Operation |
Operand |
Description
|
CU |
C |
Count up (increment)
|
CD |
C |
Count down (decrement)
|
S |
C |
Set counter
|
R |
C |
Reset counter
|
FR |
C |
Enable counter
|
Word instructions
Operation |
Operand |
Description
|
AW |
|
AND ACCU1-L (AND word)
|
AD |
|
AND ACCU1 (AND double word)
|
OW |
|
OR ACCU1-L (OR word)
|
OD |
|
OR ACCU1 (OR double word)
|
XOW |
|
Exclusive-OR ACCU (XOR word)
|
XOD |
|
Exclusive-OR ACCU (XOR double word)
|
|
Const |
with a word or double word constant
|
|
|
with ACCU2
|
Arithmetic instructions
Operation |
Operand |
Description
|
==I |
|
Integer values equal
|
<>I |
|
Integer values unequal
|
>I |
|
Integer values greater
|
>=I |
|
Integer values greater or equal
|
<I |
|
Integer values less
|
<=I |
|
Integer values less or equal
|
==D |
|
Double integer values equal
|
<>D |
|
Double integer values unequal
|
>D |
|
Double integer values greater
|
>=D |
|
Double integer values greater or equal
|
<D |
|
Double integer values less
|
<=D |
|
Double integer values less or equal
|
==R |
|
Real values equal
|
<>R |
|
Real values unequal
|
>R |
|
Real values greater
|
>=R |
|
Real values greater or equal
|
<R |
|
Real values less
|
<=R |
|
Real values less or equal
|
SIN |
|
Sine of a real value
|
COS |
|
Cosine of a real value
|
TAN |
|
Tangent of a real value
|
ASIN |
|
Arcsine of a real value
|
ACOS |
|
Arccosine of a real value
|
ATAN |
|
Arctanget of a real value
|
SQR |
|
Square a real value
|
SQRT |
|
Square root a real value
|
EXP |
|
e to the power of a real value
|
LN |
|
Natural logarithm of a real value
|
+I |
|
Integer addition
|
-I |
|
Integer subtraction
|
*I |
|
Integer multiplication
|
/I |
|
Integer division
|
+D |
|
Double-integer addition
|
-D |
|
Double-integer subtraction
|
*D |
|
Double-integer multiplication
|
/D |
|
Double-integer division
|
+R |
|
Real addition
|
-R |
|
Real subtraction
|
*R |
|
Real multiplication
|
/R |
|
Real division
|
MOD |
|
Double integer division (modulo)
|
+ |
Const |
Add a constant
|
+P# |
Const |
Add a pointer
|
DEC |
|
decrement ACCU1-LL (one byte)
|
INC |
|
increment ACCU1-LL (one byte)
|
Data type conversion instructions
Operation |
Operand |
Description
|
ITD |
|
Convert integer to double integer
|
ITB |
|
Convert integer to BCD
|
DTB |
|
Convert double integer to BCD
|
DTR |
|
Convert double integer to real
|
BTI |
|
Convert BCD to integer
|
BTD |
|
Convert BCD to double integer
|
RND |
|
Convert real to double integer (round)
|
RND+ |
|
Convert real to double integer (round up)
|
RND- |
|
Convert real to double integer (round down)
|
TRUNC |
|
Convert real to double integer (truncate)
|
INVI |
|
Invert ACCU1-L (integer)
|
INVD |
|
Invert ACCU1 (double integer)
|
NEGI |
|
Negate ACCU1-L (integer)
|
NEGD |
|
Negate ACCU1 (double integer)
|
NEGR |
|
Negate ACCU1 (real)
|
ABS |
|
REAbsolute value (real)
|
Jump instructions
Operation |
Operand |
Description
|
JU |
Destination |
Jump unconditional
|
JC |
Destination |
Jump if RLO = 1
|
JCB |
Destination |
Jump if RLO = 1 (save RLO)
|
JCN |
Destination |
Jump if RLO = 0
|
JNB |
Destination |
Jump if RLO = 0 (save RLO)
|
JBI |
Destination |
Jump if BR = 1
|
JNBI |
Destination |
Jump if BR = 0
|
JZ |
Destination |
Jump if compare result = 0
|
JN |
Destination |
Jump if compare result ≠ 0
|
JP |
Destination |
Jump if compare result > 0
|
JPZ |
Destination |
Jump if compare result >= 0
|
JM |
Destination |
Jump if compare result < 0
|
JMZ |
Destination |
Jump if compare result <= 0
|
JUO |
Destination |
Jump if compare result "Unordered Math Instruction"
|
JO |
Destination |
Jump on overflow
|
JOS |
Destination |
Jump on saved overflow
|
JL |
Destination |
Jump distributor
|
LOOP |
Destination |
Loop programming (decrement ACCU1-L and jump if ≠ 0
|
Block call instructions
Operation |
Operand |
Description
|
CALL FB |
|
Unconditional call of an FB with parameter transfer
|
CALL FC |
|
Unconditional call of an FC with parameter transfer
|
CALL SFB |
|
Unconditional call of an SFB with parameter transfer
|
CALL SFC |
|
Unconditional call of an SFC with parameter transfer
|
UC FB |
|
Unconditional call of an FB without parameter transfer
|
CC FB |
|
Conditional call of an FB without parameter transfer
|
UC FC |
|
Unconditional call of an FC without parameter transfer
|
CC FC |
|
Conditional call of an FC without parameter transfer
|
BEU |
|
End block unconditionally
|
BEC |
|
End block conditionally (RLO = 1)
|
BE |
|
End block
|
OPN |
DB |
Open data block
|
|
DI |
Open instance data block
|
TDB |
|
Exchange data block registers
|
Indirect adressing instructions
Operation |
Operand |
Funktionsbeschreibung
|
LAR1 |
|
Load AR1
|
LAR2 |
|
Load AR2
|
|
MD |
with memory double word
|
|
LD |
with local data double word
|
|
DBD |
with datablock double word
|
|
DID |
with instance data block double word
|
LAR1 |
|
Load AR1 with ACCU1
|
LAR2 |
|
Load AR2 with ACCU1
|
LAR1 |
AR2 |
Load AR1 with AR2
|
LAR1 |
P# |
Load AR1 with pointer
|
LAR2 |
P# |
Load AR2 with pointer
|
TAR1 |
|
Transfer in AR1
|
TAR2 |
|
Transfer in AR2
|
|
MD |
in memory double word
|
|
LD |
in local data double word
|
|
DBD |
in datablock double word
|
|
DID |
in instance data block double word
|
TAR1 |
|
Transfer AR1 in ACCU1
|
TAR2 |
|
Transfer AR2 in ACCU1
|
TAR1 |
AR2 |
Transfer AR1 in AR2
|
TAR |
|
Swap AR1 with AR2
|
+AR1 |
|
Add ACCU1 to AR1
|
+AR2 |
|
Add ACCU1 to AR2
|
+AR1 |
P# |
Add pointer to AR1
|
+AR2 |
P# |
Add pointer to AR2
|
Program display and null operation instructions
Operation |
Operand |
Funktionsbeschreibung
|
NOP |
0 |
Null operation instruction
|
NOP |
1 |
Null operation instruction
|
BLD |
Const |
Program display instruction (null operation)
|