S7-SoftPLC:Configuring SoftNet PN IO with PLC43.INI
From IBHsoftec Wiki English
The driver allows to exchange data from the PLC-program via SFC 14/15 with PROFINET® IO slaves over PROFINET® IO SoftNet®.
Furthermore the SFB 52/53 are available for diagnostic functions as well as reading and writing records to the PROFINET® IO device.
Parameterisation of PnioSn.dll with PLC43.INI
The PnioSn.dll must be integrated in the section [OEM].
[OEM] dll0=pniosn.dll
Furthermore the PnioSn.dll expects a section [PNIOSN], with the following parameters:
Parameter | Default value, possible values | Description |
---|---|---|
SlotNumber | 3 | Port number set in SoftNet |
TypeFC | 0, 1 | Use standard SFC/SFB |
SFC14 | 14, 1 ... 255 | Block DPRD_DAT is FC Nr |
SFC15 | 15, 1 ... 255 | Block DPWR_DAT is FC Nr |
SFB52 | 52, 1 ... 255 | Block RDREC is FC Nr |
SFB53 | 53, 1 ... 255 | Block WRREC is FC Nr |
The following example uses the application in the PC-Station on SlotNumber 3, function blocks as FC/FB and uses the FC/FB numbers equivalent to the SFC/SFB numbers:
[PNIOSN] SlotNumber=3 TypeFC=1 SFC14=14 SFC15=15 SFB52=52 SFB53=53