S7-SoftPLC:NVRAM configuration with the PLC43.INI

From IBHsoftec Wiki English
Revision as of 08:30, 23 January 2013 by Jonas (Talk | contribs)

Jump to: navigation, search

The NVRAM driver allows a remanent behavior of S7-SoftPLC.

The driver creates a file for the retain data. Depending on the capabilities of the used file system and the size of the parameterised values, the saving process will take some time, so that the process does not take place in real-time.

See "[[../NVRAM.htm#File_stystem|comment on file systems]]"


Settings in configuration file PLC43.INI

To activate the driver, the entry DLLn=NVRAMDLL.dll in section [OEM] must be made.

The driver expects the section [IBHNVRAM] where further parameters are defined.

Name of parameters Default value Description
RemFolder(required) Fully qualified path to retain data
WriteInterval(optional) 10 Time interval in milliseconds for the saving thread
WritePrio(optional) THREAD_PRIORITY_IDLE Windows thread priority for the saving thread
ShowFC(optional) 0 Show status block as FC

0 = SFC, 1 = FC.

SFCNo(optional) 212 Status block number
The sign '#' is a wild-card for a number between 0 an 99
TYP# Remanent type; M=Flag, D=data block, T=Timer, Z=Counter
LEN# Length of data that is kept remanent starting from address 0
DBNR# Data block number – must be given at TYP = D only

Example with 1000 flagbytes, 4 counters, 8 timers and 16 bytes from DB10:

[OEM]
dll0=NVRamDll.dll
[IBHNVRAM]
RemFolder=F:\SoftPLC-NVRAM\
TYP0=M
LEN0=1000
TYP1=Z
LEN1=4
TYP2=T
LEN2=8
TYP3=D
LEN3=16
DBNR3=10