Line 1: |
Line 1: |
− | [[Image:Konf_TwinCAT.png|frame|none]]
| |
| | | |
− |
| |
− | '''Default'''
| |
− |
| |
− | Resets the default values.
| |
− |
| |
− |
| |
− | '''Don't stop fieldbus on PLC stop (only set outputs to 0'''
| |
− |
| |
− | Instead of stopping the fieldbus at PLC STOP completely, all outputs are set to 0.
| |
− |
| |
− |
| |
− | '''Show TwinCAT SFCs as FCs'''
| |
− |
| |
− | Defines, whether blocks should be displayed as FCs or SFCs in ''S7-SoftPLC''.
| |
− |
| |
− |
| |
− | '''Show SFC 14/15'''
| |
− |
| |
− | Shows SFC 14/15.
| |
− |
| |
− |
| |
− | '''Port Number (as defined in the Twincat System Manager)'''
| |
− |
| |
− | Port number of the TwinCAT I/O task, normally 301.
| |
− |
| |
− |
| |
− | '''Control SFC Number (additional Ports)'''
| |
− |
| |
− | Block number of the Control SFC to read or write data from/to additional tasks.
| |
− |
| |
− |
| |
− | '''FB "GetDeviceIdentification" Number'''
| |
− |
| |
− | Block number of the FB "GetDeviceIdentification".
| |
− |
| |
− |
| |
− | '''FB "AdsRead" Number'''
| |
− |
| |
− | Block number of the FB "AdsRead".
| |
− |
| |
− |
| |
− | '''FB "AdsWrite Number'''
| |
− |
| |
− | Block number of the FB "AdsWrite".
| |
− |
| |
− | === Load configuration from TwinCAT System Manager ===
| |
− |
| |
− | In order to avoid double documentation and to be able to reuse symbols, a converter exists, that allows to covert STEP<sup>®</sup>7 symbols from symbolic table (*.SEQ) data into I/O-tasks. And to inversely convert symbols from I/O-tasks into symbolic tables.
| |
− |
| |
− | Existing symbolic tables can be applied to existing tasks with multiple options.
| |
− |
| |
− |
| |
− | '''Export symbolic tables out of the symbol editor with STEP<sup>®</sup>7.'''
| |
− | * Open symbolic table in STEP<sup>®</sup>7 symbol editor.
| |
− | * Select menu item "Table -> export".
| |
− | * Select "Allocation map (*.SEQ)" format in the following dialogue.
| |
− |
| |
− |
| |
− | '''Import symbolic tables with STEP<sup>®</sup>7 symbol editor.'''
| |
− | * Open symbolic table in STEP<sup>®</sup>7 symbol editor.
| |
− | * Select menu item "Table -> import".
| |
− | * Select "Allocation map (*.SEQ)" format in the following dialogue.
| |
− | * ''S7 for Windows''<sup>®</sup> projects generally work with SEQ files. Therefore a symbol file with the same name has to be generated, to be exchanged via the Windows<sup>®</sup> Explorer, only.
| |
− |
| |
− |
| |
− | '''Existing IO Tasks'''
| |
− |
| |
− | In this window, I/O tasks and loaded System Manager files (.tsm) are displayed.
| |
− |
| |
− | By highlighting an I/O task, it is loaded, so that it can be exported into a symbolic table.
| |
− |
| |
− |
| |
− | '''Open System Manager file'''
| |
− |
| |
− | Loads a System Manager file (.tsm) into the dialogue, to export the available symbols into a symbolic table.
| |
− |
| |
− |
| |
− | '''Export into symbolic table'''
| |
− |
| |
− | Exports the loaded I/O task into a symbolic table (.seq).
| |
− |
| |
− |
| |
− | '''Open symbolic table'''
| |
− |
| |
− | Loads a symbolic table (.seq) into the dialogue, to export the containing symbols into a I/O task.
| |
− |
| |
− |
| |
− | '''Apply symbolic table to task'''
| |
− |
| |
− | Exports the loaded symbols into a System Manager file (.tsm.).
| |
− |
| |
− |
| |
− | '''Content of symbolic table'''
| |
− |
| |
− | Shows the loaded symbols of a System Manager file (.tsm) or a symbolic table (.seq).
| |
− |
| |
− | === Using a Beckhoff EtherCAT<sup>®</sup>->PROFIBUS<sup>®</sup> coupler ===
| |
− |
| |
− | The Beckhoff EtherCAT<sup>®</sup>->PROFIBUS<sup>®</sup> coupler has got a fixed 100ms-KBus-watchdog. Without this fixed setting the PROFIBUS<sup>®</sup> would not clock correctly any more. Minimum cycle is < 100ms, if BKs/KLs are used.
| |
− |
| |
− | That means there has to be one task, that is quicker than 100ms and has the highest priority, because the task with the highest priority triggers the PROFIBUS<sup>®</sup>.
| |