OPCServer:Create Variables with Intouch FS Gateway: Difference between revisions

From IBHsoftec Wiki English
Jump to navigation Jump to search
No edit summary
No edit summary
Line 31: Line 31:
'''<Access-Path>.<Item Name>'''.  
'''<Access-Path>.<Item Name>'''.  
:The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor.
:The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor.
:The '''<Access-Path>''' is not necessary in our sample, da dieser im '''<OPC Item ID Prefix>''' schon angelegt wurde.
:The '''<Access-Path>''' is not necessary in our sample, because it is aready defined within '''<OPC Item ID Prefix>''' .
:Um auf im IBH OPC Editor definierte Variablen zuzugreifen muss der Eintrag wie folgt lauten::'''Generic.<Variablenname>'''
:To access teh variabels which are already definde wothin the  IBH OPC Editor the correct syntaxis:
:'''Generic.<Variablenname>'''




* The configuration is now completed and the variables/registers can be used:
* The configuration is now completed and the variables/registers can be used:
[[Image:FS gateway Leuchtmelder.png|552px]]
[[Image:FS gateway Leuchtmelder.png|552px]]

Revision as of 14:38, 29 October 2012

Create Variables with Intouch FS Gateway

To create Variables with Intouch FS Gateway with Intouch, please follow the description step by step.

  • Start the ArchestrA System Management Console
Start ⇒ Programme ⇒ Wonderware ⇒ System Management Console
  • Add a OPC Node via <Add OPC Object> with the name IBH:

As <Server Node> enter the IP Address of the PC , where the IBH OPC Server is running:
As <Server Name> choose the IBH OPC Server:


  • Add a OPC Group with the name OPC_Server:

Within the filed <OPC Item ID Prefix> the name of the PLC can be entered, which was created within IBH OPC Editor f.e. PLC1 followed by a dot.
Dadurch kann die Angabe <Access-path> bei der späteren <Item> Erstellung entfallen.


  • Starte the Intouch WindowMaker and create a new Acess name f.e. IBH_OPC :

As <Node name> enter the IP Address of the PC , where the IBH OPC Server is running:
As <Application name> enter FSGateway.
The <Topic-Name> is the combination of Node name IBH and OPC Group name OPC_Server.


  • Now the Variables can be created:

Select the newly created access name IBH_OPC.
The entry <Item> consists of :

<Access-Path>.<Item Name>.

The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor.
The <Access-Path> is not necessary in our sample, because it is aready defined within <OPC Item ID Prefix> .
To access teh variabels which are already definde wothin the IBH OPC Editor the correct syntaxis:
Generic.<Variablenname>


  • The configuration is now completed and the variables/registers can be used: