Difference between revisions of "S5/S7 for Windows:S5 Programming via SINEC L2"
(→Establishing a connection to a SIMATIC® S5 PLC via SINEC L2/PROFIBUS using a modern PC) |
m |
||
(2 intermediate revisions by 2 users not shown) | |||
Line 29: | Line 29: | ||
[[Image:IBHLink-S7-CP5431-profibus.jpg|400px]] | [[Image:IBHLink-S7-CP5431-profibus.jpg|400px]] | ||
− | The external 24 V power supply for the '''IBH Link S7++''' must be connected, when using it with a S5 PLC. . | + | The external 24 V power supply for the '''IBH Link S7++''' must be connected, when using it with a S5 PLC. |
+ | |||
+ | The Profibus CP must be connected to the PG port of the CPU via the so called '''monkey swing'''. '''[https://download.ibhsoftec.com/Customer/S5_Monkey_Swing.pdf Pin Out ]''' | ||
Within the online tree select '''<Network>''' and choose '''<New S5-SINEC-L2 Station..>''' using the right mosue button: | Within the online tree select '''<Network>''' and choose '''<New S5-SINEC-L2 Station..>''' using the right mosue button: | ||
Line 39: | Line 41: | ||
This allows the programming via SINEC L2/PROFIBUS using the '''IBH Link S7++'''. | This allows the programming via SINEC L2/PROFIBUS using the '''IBH Link S7++'''. | ||
Details about the setup of the SINEC-L2 connection can be found at: | Details about the setup of the SINEC-L2 connection can be found at: | ||
− | * [[IBHLink S7++: | + | * [[IBHLink S7++:SIMATIC® S5 for Windows®|Access to a SIMATIC® S5 with ''S5 for Windows®'' via SINEC L2]] |
Latest revision as of 10:12, 12 January 2022
Establishing a connection to a SIMATIC S5 PLC via SINEC L2/PROFIBUS using a modern PC
Because of IT security issues, only PCs with current operating systems including latest OS security updates and virus scanner updates are allowed to be used in corporate networks. The usage of old PCs, that allowed programming via SINEC L2/PROFIBUS is often no longer permitted and therefore no more possible.
In many production environments with old SIMATIC S5 PLCs, often SINEC L2/PROFIBUS is used to communicate with the control level or scada via Ethernet. Since it is also possible to program the PLC via SINEC L2/PROFIBUS, this task must now be performed with modern PCs.
Soft and Hardware requirements:
- A PC with a standard ethernet network card.
- Our IBHLink S7++.
- Windows XP, VISTA, 7 or 8 (32-Bit or 64-Bit).
First, a conversion of the SINEC L2/PROFIBUS network to modern twisted pair cabling with standard RJ45 connectors must be done. To do the physical media conversion, the Ethernet to PROFIBUS Gateway IBH Link S7++ is used.
Before plugging the IBH Link S7++ on PROFIBUS, the PROFIBUS parameters must be set up correctly. The actual settings of the parameters must be read out from the configuration of the used communication processor. For a S5 95U with PROFIBUS, the parameters can be found within the DB1. If a CP5431 is used, the COM package COM5430 delivers the required information.
The parameters can be set in the IBH Link S7++ with a standard webbrowser. Likewise, the bus parameters can also be configured with the IBHNet configuration tool.
IBH Link S7++ on the PROFIBUS connector of a S5 95U
IBH Link S7++ on the PROFIBUS connector of a CP5431
The external 24 V power supply for the IBH Link S7++ must be connected, when using it with a S5 PLC.
The Profibus CP must be connected to the PG port of the CPU via the so called monkey swing. Pin Out
Within the online tree select <Network> and choose <New S5-SINEC-L2 Station..> using the right mosue button:
Setup of an SINEC-L2 connection
This allows the programming via SINEC L2/PROFIBUS using the IBH Link S7++. Details about the setup of the SINEC-L2 connection can be found at: