Difference between revisions of "IBHLink S5++:SIMATIC® S5 WinCC flexible"
| Line 32: | Line 32: | ||
The ethernet communication driver for S7 300/400 must be selected in WinCC flexible, since only this driver allows the selection of an extension slot on the PLC side. | The ethernet communication driver for S7 300/400 must be selected in WinCC flexible, since only this driver allows the selection of an extension slot on the PLC side. | ||
| + | |||
[[Image:WinCCFlex_Connections.png|766px]] | [[Image:WinCCFlex_Connections.png|766px]] | ||
| + | |||
| + | {| class="wikitable" | ||
| + | |- | ||
| + | ! S5 !! S7 | ||
| + | |- | ||
| + | | DL 0 || DBB 0 | ||
| + | |- | ||
| + | | DR 0 || DBB 1 | ||
| + | |- | ||
| + | | DL 1 || DBB 2 | ||
| + | |- | ||
| + | | DR 1 || DBB 3 | ||
| + | |- | ||
| + | | DL 2 || DBB 4 | ||
| + | |- | ||
| + | | DR 2 || DBB 5 | ||
| + | |} | ||
| + | or | ||
| + | {| class="wikitable" | ||
| + | |- | ||
| + | | DW 0 || DBW 0 | ||
| + | |- | ||
| + | | DW 1 || DBW 2 | ||
| + | |- | ||
| + | | DW 2 || DBW 4 | ||
| + | |} | ||
If you are using the WinCC flexible Runtime, please check that in the settings of the PG/PC Interface the correct driver ''TCP/IP'' for the Access Point ''S7ONLINE'' is chosen. | If you are using the WinCC flexible Runtime, please check that in the settings of the PG/PC Interface the correct driver ''TCP/IP'' for the Access Point ''S7ONLINE'' is chosen. | ||
Revision as of 12:14, 19 July 2012
It is possible to realize a connection from a WinCC flexible Runtime/Panel to a SIMATIC® S5 station over ethernet using an IBHLink S5++ as gateway.
Example
In the following example a configuration with PcVue is shown. The HMI station is connected to the IBHLink S5++ via an Ethernet connection. The IBHLink S5++ itself is connected to a SIMATIC® S5 station on the AS511 port. Communication parameters were configured by the IBHNet configuration tool.
The following addresses were chosen in the example:
IP addresses:
| Station | Address |
|---|---|
| HMI station | 192.168.10.122 |
| IBHLink S5++ | 192.168.10.102 |
Operation with S7 HMI devices: For the operation with S7 HMI devices the following settings need to be made:
| IP address of the PLC | IP address of the IBH Link S5++ |
| Rack number of the PLC | 0 |
| Slot number of the PLC | 2 |
| MPI® address of the PLC | 2 |
Configuration:
The ethernet communication driver for S7 300/400 must be selected in WinCC flexible, since only this driver allows the selection of an extension slot on the PLC side.
| S5 | S7 |
|---|---|
| DL 0 | DBB 0 |
| DR 0 | DBB 1 |
| DL 1 | DBB 2 |
| DR 1 | DBB 3 |
| DL 2 | DBB 4 |
| DR 2 | DBB 5 |
or
| DW 0 | DBW 0 |
| DW 1 | DBW 2 |
| DW 2 | DBW 4 |
If you are using the WinCC flexible Runtime, please check that in the settings of the PG/PC Interface the correct driver TCP/IP for the Access Point S7ONLINE is chosen.
The configuration of the connection is now completed and you can continue with defining your Tags.