Difference between revisions of "Mitsubishi Electric IoT Gateway:backplane bus"
From IBHsoftec Wiki English
(Created page with "If the RD55 is plugged on the same rack as the CPU no RJ45 cable is needed. The communication can be done directly via the backplane bus. Image:Mitsubishi_RD55_Controllers...") |
m |
||
(2 intermediate revisions by the same user not shown) | |||
Line 1: | Line 1: | ||
− | If the RD55 is plugged on the same rack as the CPU no | + | If the RD55 is plugged on the same rack as the CPU no Ethernet cable is needed. |
The communication can be done directly via the backplane bus. | The communication can be done directly via the backplane bus. | ||
[[Image:Mitsubishi_RD55_Controllers.png|470px]] | [[Image:Mitsubishi_RD55_Controllers.png|470px]] | ||
+ | |||
+ | In the field Ethernet address 4 times the zero needs to be entered: | ||
[[Image:Mitsubishi_RD55_Insert_Station.png|441px]] | [[Image:Mitsubishi_RD55_Insert_Station.png|441px]] | ||
[[Image:Mitsubishi_RD55_Insert_CPU.png|569px]] | [[Image:Mitsubishi_RD55_Insert_CPU.png|569px]] |
Latest revision as of 13:23, 4 April 2022
If the RD55 is plugged on the same rack as the CPU no Ethernet cable is needed. The communication can be done directly via the backplane bus.
In the field Ethernet address 4 times the zero needs to be entered: