Difference between revisions of "IBH Link UA:Configuration with TIA Portal"
(→TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++) |
|||
Line 101: | Line 101: | ||
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S71200.zip TIA Sample: IBH Link UA S7-1200]''' | '''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S71200.zip TIA Sample: IBH Link UA S7-1200]''' | ||
− | ==TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++== | + | ==TIA Sample: IBH Link UA S7-315-2 DP routet via [http://www.ibhsoftec.com/IBH-Link-S7-PP-Eng IBH Link S7++]== |
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S7_315_Routing_TIA.zip TIA Beispiel: IBH Link UA S7-315-2 DP routet via IBH Link S7++]''' | '''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S7_315_Routing_TIA.zip TIA Beispiel: IBH Link UA S7-315-2 DP routet via IBH Link S7++]''' | ||
− | |||
− | |||
==TIA Sample: IBH Link UA S5 95U via IBH Link S5++== | ==TIA Sample: IBH Link UA S5 95U via IBH Link S5++== | ||
'''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S5.zip TIA Sample: IBH Link UA S5]''' | '''Download: [http://download.ibhsoftec.com/german/Beispiele/IBH_Link_UA_S5.zip TIA Sample: IBH Link UA S5]''' |
Revision as of 15:58, 16 January 2015
Configuration of the IBH Link UA with TIA portal
Contents
Example
In the following example, the configuration with TIA Portal V13 is shown.
The S7-1500 station is connected with the IBH Link UA via Ethernet.
The following addresses were chosen in the example:
IP addresses:
Station | Address |
---|---|
IBHLink UA | 192.168.10.125 |
S7-1500 | 192.168.10.129 |
Configuration:
A new device will be added (in the sample a S7-1500):
The S7-1500 will be connected with Ethernet Subnet PNIE_1 and the IP address must be set:
Full access and access with PUT/GET communication is necessary:
Now a DB can be created:
The Optimized block access must be deactivated:
Within OB1 the data word 1 and flag word 1 will be counted in our example:
Flag word 1 is now listed as standard tag:
As next step a Simatic PC Station must be added:
After adding an OPC Server in slot 1 and an IE-module in slot 2, the version of the OPC Server must be changed form version V12 to V8:
Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH Links UA must be entered:
Now a S7 connection between the OPC Server and the PC station must be established:
Within the properies of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:
Now the configuration needs to be downloaded to the PLC:
and to the IBH Link UA:
The configuration is now completed and the tags from the IBH link UA are available .
TIA Sample: IBH Link UA S7-1200
Download: TIA Sample: IBH Link UA S7-1200
TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++
Download: TIA Beispiel: IBH Link UA S7-315-2 DP routet via IBH Link S7++
TIA Sample: IBH Link UA S5 95U via IBH Link S5++
Download: TIA Sample: IBH Link UA S5