Difference between revisions of "IBHLink S7++:S7-300/S7-400 PcVue"

From IBHsoftec Wiki English
Jump to: navigation, search
Line 41: Line 41:
 
[[Image:PcVue_Frame_creation.png|543px]]<br />
 
[[Image:PcVue_Frame_creation.png|543px]]<br />
 
<br />
 
<br />
After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate>
+
After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate>:<br />
 
[[Image:PcVue_Select_communication_objects.png|556px]]<br />
 
[[Image:PcVue_Select_communication_objects.png|556px]]<br />
 
+
<br />
 +
Within the Application Explorer you can add a Registe
 
[[Image:PcVue_configure_application_explorer.png|174px]]<br />
 
[[Image:PcVue_configure_application_explorer.png|174px]]<br />
 
+
<br />
 
[[Image:PcVue_Register_variable_creation.png|551px]]<br />
 
[[Image:PcVue_Register_variable_creation.png|551px]]<br />
 
+
<br />
[[Image:PcVue_animate_text.png|590px]]<br />
+
 
+
 
The configuration is now completed and the Tags can be used:<br />
 
The configuration is now completed and the Tags can be used:<br />
 
 
[[Image:PcVue_Trend_setting.png|919px]]<br />
 
[[Image:PcVue_Trend_setting.png|919px]]<br />
 
+
<br />
 
[[Image:PcVue_Trend.png|564px]]<br />
 
[[Image:PcVue_Trend.png|564px]]<br />

Revision as of 16:29, 14 June 2012

It is possible to realize a connection from a PC with PcView to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.

Example

In the following example a configuration with PcView is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S7++ 192.168.10.125

MPI addresses:

Station Address
IBHLink S7++ 17
S7-300/S7-400 station 2

Configuration:

The ethernet communication driver for S7-300/400 named SIEMENS IP ISO-S7 must be selected by double clicking the line *CREATION* below Network :
PcVue Equipment.png

PcVue Network creation.png

By double clicking the line *CREATION* below <Node>:you can enter the IP address of the IBH Link S7++.
As <Equipment type> please select S7300/400
PcVue node parameter.png

By double clicking the line *CREATION* below <Frame the needed variables can be choosen>
PcVue Frame creation.png

After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate>:
PcVue Select communication objects.png

Within the Application Explorer you can add a Registe PcVue configure application explorer.png

PcVue Register variable creation.png

The configuration is now completed and the Tags can be used:
PcVue Trend setting.png

PcVue Trend.png