Difference between revisions of "IBHLink S7++:S7-300/S7-400 PcVue"
Line 41: | Line 41: | ||
[[Image:PcVue_Frame_creation.png|543px]]<br /> | [[Image:PcVue_Frame_creation.png|543px]]<br /> | ||
<br /> | <br /> | ||
− | After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate> | + | After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate>:<br /> |
[[Image:PcVue_Select_communication_objects.png|556px]]<br /> | [[Image:PcVue_Select_communication_objects.png|556px]]<br /> | ||
− | + | <br /> | |
+ | Within the Application Explorer you can add a Registe | ||
[[Image:PcVue_configure_application_explorer.png|174px]]<br /> | [[Image:PcVue_configure_application_explorer.png|174px]]<br /> | ||
− | + | <br /> | |
[[Image:PcVue_Register_variable_creation.png|551px]]<br /> | [[Image:PcVue_Register_variable_creation.png|551px]]<br /> | ||
− | + | <br /> | |
− | + | ||
− | + | ||
The configuration is now completed and the Tags can be used:<br /> | The configuration is now completed and the Tags can be used:<br /> | ||
− | |||
[[Image:PcVue_Trend_setting.png|919px]]<br /> | [[Image:PcVue_Trend_setting.png|919px]]<br /> | ||
− | + | <br /> | |
[[Image:PcVue_Trend.png|564px]]<br /> | [[Image:PcVue_Trend.png|564px]]<br /> |
Revision as of 16:29, 14 June 2012
It is possible to realize a connection from a PC with PcView to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.
Example
In the following example a configuration with PcView is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.
The following addresses were chosen in the example:
IP addresses:
Station | Address |
---|---|
HMI station | 192.168.10.122 |
IBHLink S7++ | 192.168.10.125 |
MPI addresses:
Station | Address |
---|---|
IBHLink S7++ | 17 |
S7-300/S7-400 station | 2 |
Configuration:
The ethernet communication driver for S7-300/400 named SIEMENS IP ISO-S7 must be selected by double clicking the line *CREATION* below Network :
By double clicking the line *CREATION* below <Node>:you can enter the IP address of the IBH Link S7++.
As <Equipment type> please select S7300/400
By double clicking the line *CREATION* below <Frame the needed variables can be choosen>
After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate>:
Within the Application Explorer you can add a Registe
The configuration is now completed and the Tags can be used: