OPCServer:Create Variables manually with Intouch

From IBHsoftec Wiki English
Jump to navigation Jump to search

Intouch with the IBHsoftec OPC Server V4.x

HOWTO create variables manually

Please run the Intouch programm OPCLink.

Select <Configure> <Topic Defintions>



Define a topic Name (i.e. IBH_OPC ).

In the entry field OPC Server Name please select the server IBHSoftec.IBHOPC.DA.1.

The entry OPC Path must stay empty.

Please run the Intouch WindowMaker:

Create a new access name :




Select the newly created access name.

The entry <Item> consists of :

<D><Access-Path>.<Item Name>

In our sample : DS7_300.M1.0

Whereby the <D> is the notation for Discrete.

Following values are possible :

d discrete value
i integer value
r real value
m message value

The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor:




The OPC variables may now be used in the WindowMaker.