IBH OPC UA:Loading multible projects into the IBH Link UA

From IBHsoftec Wiki English
Jump to navigation Jump to search

Using multiple STEP7 and / or TIA projects in parallel

It may happen that not all controllers can be integrated in a common project. Therefore, several individual projects can be loaded into the IBH OPC UA Server/Client . Each project must be loaded in a separate slot for this purpose.

The IBH OPC UA Server/Client can handle up to 31 STEP7 and / or TIA projects in parallel.

Configuration with the TIA Portal

The Ethernet CP must be placed on slot 2 (within TIA Portal named Index)

Attention!

The configuration of the Ethernet CP MUST be identical in ALL individual projects

For the OPC Server the slots 1 and 3-32 can be used:

The slots represent each individual projects:

Configuration with STEP7

The Ethernet CP must be placed on slot 2

Attention!

The configuration of the Ethernet CP MUST be identical in ALL individual projects

For the OPC Server the slots 1 and 3-32 can be used:

The slots represent each individual projects:

OPC Slots

The sample shows a TIA project from a S7-1200 and a STEP7 project from a S7-315-2 DP:

Using the web interface selectd or all slots can be deleted.

Forbid project download with STEP®7 or TIA Portal

An unintentional overwriting of the configuration can be prevented: