IBH Link UA:Loading multible projects into the IBH Link UA

From IBHsoftec Wiki English
Revision as of 17:12, 9 March 2015 by Axel (Talk | contribs)

(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

Using multiple STEP7 and / or TIA projects in parallel

It may happen that not all controllers can be integrated in a common project. Therefore, several individual projects can be loaded into the IBH Link UA . Each project must be loaded in a separate slot for this purpose.

The IBH Link UA can handle up to 31 STEP7 and / or TIA projects in parallel.

Configuration with the TIA Portal

The Ethernet CP must be placed on slot 2 (within TIA Portal named Index)

ACHTUNG.png

Attention!

The configuration of the Ethernet CP MUST be identical in ALL individual projects

IBH Link UA CP Index Eng.png

For the OPC Server the slots 1 and 3-32 can be used:

IBH Link UA OPC Index Eng.png

The slots represent each individual projects:

IBH Link UA Slott1 Eng.png

Configuration with STEP7

The Ethernet CP must be placed on slot 2

ACHTUNG.png

Attention!

The configuration of the Ethernet CP MUST be identical in ALL individual projects

For the OPC Server the slots 1 and 3-32 can be used:

IBH Link UA CP OPC Index Eng.png

The slots represent each individual projects:

IBH Link UA Slot Eng.png

OPC Slots

The sample shows a TIA project from a S7-1200 and a STEP7 project from a S7-315-2 DP:

IBH Link UA Slott1 3 Eng.png

Using the web interface selectd or all slots can be deleted.

Forbid project download with STEP®7 or TIA Portal

An unintentional overwriting of the configuration can be prevented:

IBH Link UA forbid download.png