OPCServer:Create Variables manually with Intouch

From IBHsoftec Wiki English
Revision as of 07:55, 25 June 2012 by Jonas (Talk | contribs)

Jump to: navigation, search

Intouch® with the IBHsoftec OPC Server V4.x

HOWTO create variables manually

Please run the Intouch® programm OPCLink.

Select <Configure> <Topic Defintions>

OPC InTouch man1.jpg


OPC InTouch man2.jpg


Define a topic Name (i.e. IBH_OPC ).

In the entry field OPC Server Name please select the server IBHSoftec.IBHOPC.DA.1.

The entry OPC Path must stay empty.

Please run the Intouch WindowMaker:

Create a new access name :


OPC InTouch man3.jpg


OPC InTouch man4.jpg


Select the newly created access name.

The entry <Item> consists of :

<D><Access-Path>.<Item Name>

In our sample : DS7_300.M1.0

Whereby the <D> is the notation for Discrete.

Following values are possible :

d discrete value
i integer value
r real value
m message value

The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor:


ProTool6 3.jpg


OPC InTouch man6.jpg


The OPC variables may now be used in the WindowMaker.