IBH OPC UA:Configuration with STEP7

From IBHsoftec Wiki English
Revision as of 11:29, 17 March 2016 by Axel (Talk | contribs)

(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

Configuration of the IBH OPC UA Server/Client with STEP7

Example

In the following example the configuration with STEP7 is shown.

The S7 IM151-8 station is connected with the IBH OPC UA Server/Client via Ethernet.

The following addresses were chosen in the example:

IP addresses:

Station Address
IBH OPC UA Server/Client 192.168.10.125
S7-1500 192.168.10.129

Configuration:

A new device will be added (in the sample a S7 IM151-8) and networked with Ethernet(1):

IBH Link UA Step7 IM HW.png

Now a DB can be created:

IBH Link UA Step7 DB eng.png

IBH Link UA Step7 hint.png

In our sample the symbols Data and Flagword 1 are defined within the symbolic table:

IBH Link UA Step7 symbol table.png

Within OB1 the data word 1 and flag word 1 will be counted in our example:

IBH Link UA Step7 OB eng.png

After downloading the blocks OB1 and DB1 to the IM151-8 a Simatic PC Station must be added:

IBH Link UA Step7 add station.png


Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH OPC UA Server/Client must be entered

after adding an OPC Server in slot 1 and an IE-module in slot 2

IBH Link UA Step7 station.png

IBH Link UA IP.png

Now a S7 connection between the OPC Server and the PC station must be established:

IBH Link UA Step7 connection.png

Within the properies of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:

IBH Link UA Step7 configure symbols.png

Now the configuration needs to be downloaded to the PLC and the IBH OPC UA Server/Client:

IBH Link UA Step7 download stations.png

The configuration is now completed and the tags from the IBH OPC UA Server/Client are available.

IBHLink UA STEP7 OPC Client eng.png

STEP7 Sample: IBH OPC UA Server/Client with SIMATIC S5 via IBH Link S5++

Download: STEP7 Sample: IBH OPC UA Server/Client S5

STEP7 Sample: IBH OPC UA Server/Client with S7 315-2DP routet via IBH Link S7++

Download: STEP7 Sample: IBH OPC UA Server/Client with S7 315-2DP

STEP7 Sample: IBH OPC UA Server/Client with S7-200 via IBH Link S7++

Notes about the configuration can be found within the ReadMe.txt.

Download: STEP7 Sample: IBH OPC UA Server/Client with S7-200 via IBH Link S7++

STEP7 Beispiel: IBH OPC UA Server/Client with IBH SoftSPS

Download: STEP7 Sample: IBH OPC UA Server/Client with IBH SoftSPS