IBH OPC UA:Configuration with TIA Portal

From IBHsoftec Wiki English
Revision as of 11:18, 16 March 2016 by Axel (talk | contribs) (Created page with "Configuration of the '''IBH OPC Server/Client''' with TIA portal ==Example== In the following example, the configuration with TIA Portal V13 is shown. The S7-1500 station i...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Configuration of the IBH OPC Server/Client with TIA portal

Example

In the following example, the configuration with TIA Portal V13 is shown.

The S7-1500 station is connected with the IBH OPC Server/Client via Ethernet.

The following addresses were chosen in the example:

IP addresses:

Station Address
IBH OPC Server/Client 192.168.10.125
S7-1500 192.168.10.129

Configuration:

A new device will be added (in the sample a S7-1500):

The S7-1500 will be connected with Ethernet Subnet PNIE_1 and the IP address must be set:

Full access and access with PUT/GET communication is necessary:

Now a DB can be created:

The Optimized block access must be deactivated:

Within OB1 the data word 1 and flag word 1 will be counted in our example:

Flag word 1 is now listed as standard tag:

As next step a Simatic PC Station must be added:

After adding an OPC Server in slot 1 and an IE-module in slot 2, the version of the OPC Server must be changed from version V12 to V8:

Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH OPC UA Server/Client must be entered:

Now a S7 connection between the OPC Server and the PC station must be established:

461.px

Within the properties of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:

Now the configuration needs to be downloaded to the PLC:

and to the IBH OPC UA Server/Client:

The configuration is now completed and the tags from the IBH OPC UA Server/Client are available .

TIA Sample: IBH OPC UA Server/Client S7-1200

Download: TIA Sample: IBH OPC UA Server/Client S7-1200

TIA Sample: IBH OPC UA Server/Client S7-200 via IBH Link S7++

Notes about the configuration can be found within the ReadMe.txt.

Download: TIA Sample: IBH OPC UA Server/Client S7-200 via IBH Link S7++

TIA Sample: IBH OPC UA Server/Client S7-315-2 DP routed via IBH Link S7++

Download: TIA Sample: IBH OPC UA Server/Client S7-315-2 DP routet via IBH Link S7++

TIA Sample: IBH OPC UA Server/Client S5 95U via IBH Link S5++

Download: TIA Sample: IBH OPC UA Server/Client S5