IBH Link UA:Configuration with STEP7

From IBHsoftec Wiki English
Revision as of 15:06, 9 July 2015 by Axel (talk | contribs)
Jump to navigation Jump to search

Configuration of the IBH Link UA with STEP7

Example

In the following example the configuration with STEP7 is shown.

The S7 IM151-8 station is connected with the IBH Link UA via Ethernet.

The following addresses were chosen in the example:

IP addresses:

Station Address
IBHLink UA 192.168.10.125
S7-1500 192.168.10.129

Configuration:

A new device will be added (in the sample a S7 IM151-8) and networked with Ethernet(1):

Now a DB can be created:

In our sample the symbols Data and Flagword 1 are defined within the symbolic table:

Within OB1 the data word 1 and flag word 1 will be counted in our example:

After downloading the blocks OB1 and DB1 to the IM151-8 a Simatic PC Station must be added:


Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH Links UA must be entered

after adding an OPC Server in slot 1 and an IE-module in slot 2

Now a S7 connection between the OPC Server and the PC station must be established:

Within the properies of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:

Now the configuration needs to be downloaded to the PLC and the IBH Link UA:

The configuration is now completed and the tags from the IBH link UA are available.

STEP7 Sample: IBH Link UA with SIMATIC S5 via IBH Link S5++

Download: STEP7 Sample: IBH Link UA S5

STEP7 Sample: IBH Link UA with S7 315-2DP routet via IBH Link S7++

Download: STEP7 Sample: IBH Link UA with S7 315-2DP

STEP7 Sample: IBH Link UA with S7-200 via IBH Link S7++

Notes about the configuration can be found within the ReadMe.txt.

Download: STEP7 Sample: IBH Link UA with S7-200 via IBH Link S7++

STEP7 Beispiel: IBH Link UA with IBH SoftSPS

Download: STEP7 Sample: IBH Link UA with IBH SoftSPS