IBH Link UA:Configuration with TIA Portal

From IBHsoftec Wiki English
Jump to navigation Jump to search

Configuration of the IBH Link UA with TIA portal

Example

In the following example, the configuration with TIA Portal V13 is shown.

The S7-1500 station is connected with the IBH Link UA via Ethernet.

The following addresses were chosen in the example:

IP addresses:

Station Address
IBHLink UA 192.168.10.125
S7-1500 192.168.10.129

Configuration:

A new device will be added (in the sample a S7-1500):

The S7-1500 will be connected with Ethernet Subnet PNIE_1 and the IP address must be set:

Full access and access with PUT/GET communication is necessary:

Now a DB can be created:

The Optimized block access must be deactivated:

Within OB1 the data word 1 and flag word 1 will be counted in our example:

Flag word 1 is now listed as standard tag:

As next step a Simatic PC Station must be added:

After adding an OPC Server in slot 1 and an IE-module in slot 2, the version of the OPC Server must be changed form version V12 to V8:

Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH Links UA must be entered:

Now a S7 connection between the OPC Server and the PC station must be established:

461.px

Within the properies of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:

Now the configuration needs to be downloaded to the PLC:

and to the IBH Link UA:

The configuration is now completed and the tags from the IBH link UA are available .

TIA Sample: IBH Link UA S7-1200

Download: TIA Sample: IBH Link UA S7-1200

TIA Sample: IBH Link UA S7-315-2 DP routet via IBH Link S7++

Download: TIA Beispiel: IBH Link UA S7-315-2 DP routet via IBH Link S7++

TIA Sample: IBH Link UA S5 95U via IBH Link S5++

Download: TIA Sample: IBH Link UA S5