S7 Connection from Siemens LOGO! (RCE version) to a S7 PLC via IBHLink S7++ or IBHLink S7++ HS

The RCE versions from Siemens LOGO! are equiped with an Ethernet port and support S7 connections via Ethernet. This allows a data communication between LOGO! and a S7-PLC via IBH Link S7++. Process data can be exchanged between both PLC. Below there is the decription how to setup the LOGO! for data communication with the IBH Link S7++.

Communikation

The communikation with the LOGO! will be established via S7 connections. The LOGO! can read and write from data area of the S7 PLC via IBH Link S7++:

  • Inputs
  • Outputs
  • Flags
  • Content of data blocks.

Settings of the LOGO! via Display

First of all the LOGO! must be reachable via Ethernet. After that an IP addrees can be set with the LOGO! Soft Comfort software. Maybe the IP address of the PC neds to be changed, so that the LOGO! and the PC are with the same subnet. The currwent address of LOGO! is shown on the display.

  • With <ESC> you'll get to the settings.
  • Scroll down until <network> appears.
  • <OK> 'IP address'. <OK> The current adress is shown.

Settings within the LOGO!Soft Comfort software

Within the LOGO!Soft Comfort software setup the IP address of the PLC via "Extras - Transfer - Configure Network asdress".

Logo-comfort-setaddr-ger.PNG

Afte that the LOGO! must be confured, to build up Client connections to other stations.

Via "Extras - Ethernet Connections" a new connection can be added.

Logo-comfort-connections-ger.PNG

With a double click one the connection it can be configured.

Logo-comfort-softsps-ger.PNG

A Client connection must be selected. The settings for the TSAPs are local '20.00' and remote '01.nn'. 'nn' stands for the MPI address of the S7 PLC, . The syntax is Hexadecimal, which menas '01.15' stands for the address 21, '01.02' for the address 2. As operations read and write are available. The local variables relate to the intern simulated DB1. The syntax for variables from the local DB is VBn, for the remote partner is S7 Syntax.

To exchange variables with the DB1, the DB must be created. Via "Extras - Parameter VM assignment" the elements of the program can be selcted, which should be mapped within the DB1.

Logo-comfort-db1-ger.PNG

Some times the LOGO! Soft Comfort software needs to be restarted after changing the connections, to tranfer the changes to the LOGO!

Access with IBHNet object

Beginning with IBHNet V1.49 it is possible to access the LOGO! via 'RFC1006'. Die zu verwendende MPI-Adresse bei der Funktion 'Connect()' is 128, bei 'Connect_DP()' ist es der Steckplatz 128. As variables Inputs, Outputs, Flags, the DB1 and the Order No. can be selected.