IBHLink S7++ S7-300/S7-400 Elipse Scada

From IBHsoftec Wiki English
Revision as of 12:17, 4 June 2012 by Axel (Talk | contribs)

Jump to: navigation, search

It is possible to realize a connection from a PC with Elipse SCADA to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.

Example

In the following example a configuration with Elipse SCADA is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S7++ 192.168.10.125

PPI addresses:

Station Address
IBHLink S7++ 17
S7-300/S7-400 station 2

Configuration:

The ethernet communication driver for S7-300/400 named MProt.dll must be selected witin the Application Organizer: Elipse driver.png

Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address> Elipse driver settings.png


Enter the IP Address of the IBH LinkS7 ++ and choose port 102: Elipse driver settings ethernet.png

The configuration of the connection is now completed and you can continue with defining your Tags.