IBH OPC UA:Configuration with TIA Portal

From IBHsoftec Wiki English
Revision as of 12:18, 16 March 2016 by Axel (Talk | contribs)

(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

Configuration of the IBH OPC Server/Client with TIA portal

Example

In the following example, the configuration with TIA Portal V13 is shown.

The S7-1500 station is connected with the IBH OPC Server/Client via Ethernet.

The following addresses were chosen in the example:

IP addresses:

Station Address
IBH OPC Server/Client 192.168.10.125
S7-1500 192.168.10.129

Configuration:

A new device will be added (in the sample a S7-1500):

IBH Link UA add device.png

The S7-1500 will be connected with Ethernet Subnet PNIE_1 and the IP address must be set:

IBH Link UA S7 1500 PNIE.png

Full access and access with PUT/GET communication is necessary:

IBH Link UA S7 protection.png

Now a DB can be created:

IBH Link UA S7 add DB.png

The Optimized block access must be deactivated:

IBH Link UA S7 DB properties.png

IBH Link UA S7 DB eng.png

Within OB1 the data word 1 and flag word 1 will be counted in our example:

IBH Link UA S7 OB1 eng.png

Flag word 1 is now listed as standard tag:

IBH Link UA S7 standard tag.png

As next step a Simatic PC Station must be added:

IBH Link UA S7 add pc station.png

After adding an OPC Server in slot 1 and an IE-module in slot 2, the version of the OPC Server must be changed from version V12 to V8:

IBH Link UA S7 change device.png

IBH Link UA S7 device V8.png

Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH OPC UA Server/Client must be entered:

IBH Link UA S7 IE.png

IBH Link UA IP.png

Now a S7 connection between the OPC Server and the PC station must be established:

461.px

Within the properties of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:

IBH Link UA S7 PLC tags.png

IBH Link UA S7 DB tags.png

Now the configuration needs to be downloaded to the PLC:

IBH Link UA S7 dwonload plc.png

and to the IBH OPC UA Server/Client:

IBH Link UA S7 dwonload.png

The configuration is now completed and the tags from the IBH OPC UA Server/Client are available .

IBHLink UA OPC Client.png

TIA Sample: IBH OPC UA Server/Client S7-1200

Download: TIA Sample: IBH OPC UA Server/Client S7-1200

TIA Sample: IBH OPC UA Server/Client S7-200 via IBH Link S7++

Notes about the configuration can be found within the ReadMe.txt.

Download: TIA Sample: IBH OPC UA Server/Client S7-200 via IBH Link S7++

TIA Sample: IBH OPC UA Server/Client S7-315-2 DP routed via IBH Link S7++

Download: TIA Sample: IBH OPC UA Server/Client S7-315-2 DP routet via IBH Link S7++

TIA Sample: IBH OPC UA Server/Client S5 95U via IBH Link S5++

Download: TIA Sample: IBH OPC UA Server/Client S5