Revision as of 15:03, 4 December 2012
The text below describes the connection of S5 for Windows® to a SIMATIC® S5 using the IBH-USB-S5-Adapter.
The PC is connected to a SIMATIC® S5 station via the IBH-USB-S5-Adapter on the AS511 port.
Software requirements
- S5 for Windows® > V6.x
- USB Driver
The IBH USB-S5-Adapter needs to be installed correctly . This can be controled within device manager.
<Start><System Control Set><System><Device Manager>
There the entry <USB Serial Port> must appear.
Within the Onlinetree select USB Serial Port:
using the right mosue button within the settings:
choose as <Protocol> S5-AS511 with the <Baudrate> 9600.
Now the onnline connection can be established: