It is possible to realize a connection from a PC with '''PcView''' to a SIMATIC® S5 station over ethernet using an [http://www.ibhsoftec.com/IBH-Link-S5-PP-Eng IBHLink S5++] as gateway.
+
It is possible to realize a connection from a PC with '''PcVue''' to a SIMATIC® S5 station over ethernet using an [http://www.ibhsoftec.com/IBH-Link-S5-PP-Eng IBHLink S5++] as gateway.
  
 
==Example==
 
==Example==
In the following example a configuration with '''PcView''' is shown.
+
In the following example a configuration with '''PcVue''' is shown.
The HMI station is connected to the IBHLink S5++ via an Ethernet connection. The IBHLink S5++ itself is connected to a SIMATIC® S5 station by the AS511 port. Bus parameters are configured by the IBHNet configuration tool.
+
The HMI station is connected to the IBHLink S5++ via an Ethernet connection. The IBHLink S5++ itself is connected to a SIMATIC® S5 station on the AS511 port. Communication parameters were configured by the IBHNet configuration tool.
  
 
The following addresses were chosen in the example:
 
The following addresses were chosen in the example:

Revision as of 11:49, 19 June 2012

It is possible to realize a connection from a PC with PcVue to a SIMATIC® S5 station over ethernet using an IBHLink S5++ as gateway.

Example

In the following example a configuration with PcVue is shown. The HMI station is connected to the IBHLink S5++ via an Ethernet connection. The IBHLink S5++ itself is connected to a SIMATIC® S5 station on the AS511 port. Communication parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S5++ 192.168.10.102

Operation with S7 HMI devices: For the operation with S7 HMI devices the following settings need to be made:

IP address of the PLC IP address of the IBH Link S5++
Rack number of the PLC 0
Slot number of the PLC 2
MPI® address of the PLC 2

Configuration:

The ethernet communication driver for S7-300/400 named SIEMENS IP ISO-S7 must be selected by double clicking the line *CREATION* below Network :
PcVue Equipment.png

PcVue Network creation.png

By double clicking the line *CREATION* below <Node>:you can enter the IP address of the IBH Link S7++.
As <Equipment type> please select S7300/400
PcVue node parameter S5.png

By double clicking the line *CREATION* below <Frame the needed variables can be choosen>
PcVue Frame creation.png

After that the communication objects have to be activated by clicking on the buttons <ON< and <Validate>:
PcVue Select communication objects.png

Within the Application Explorer you can add a Register:
PcVue configure application explorer.png

PcVue add register.png

PcVue Register variable creation.png

The configuration is now completed and the variables/registers can be used:
PcVue Trend setting.png

PcVue Trend.png