IBHLink S5++:SIMATIC® S5 Elipse SCADA: Difference between revisions

From IBHsoftec Wiki English
Jump to navigation Jump to search
Created page with "It is possible to realize a connection from a PC with '''Elipse SCADA''' to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway. ==Example== In the following ..."
 
No edit summary
Line 7: Line 7:
The following addresses were chosen in the example:
The following addresses were chosen in the example:


IP addresses:
IP addresses:
IP addresses:
{| class="wikitable"
{| class="wikitable"
Line 14: Line 15:
| HMI station || 192.168.10.122
| HMI station || 192.168.10.122
|-
|-
| IBHLink S7++ || 192.168.10.125
| IBHLink S5++ || 192.168.10.125
|}
|}


MPI addresses:
'''Operation with S7 HMI devices:'''
For the operation with S7 HMI devices the following settings need to be made:  
{| class="wikitable"
{| class="wikitable"
|-
|-
! Station !! Address
| IP address of the PLC || IP address of the IBH Link S5++
|-
| Rack number of the PLC || 0
|-
|-
| IBHLink S7++ || 17
| Slot number of the PLC || 2
|-
|-
| S7-300/S7-400 station || 2
| MPI® address of the PLC || 2  
|}
|}
Configuration:
Configuration:


Line 36: Line 39:




Enter the IP Address of the IBH LinkS7 ++ and choose port 102:<br />
Enter the IP Address of the IBH LinkS5 ++ and choose port 102:<br />


[[Image:Elipse_driver_settings_ethernet.png|456px]]
[[Image:Elipse_driver_settings_ethernet.png|456px]]

Revision as of 14:19, 18 June 2012

It is possible to realize a connection from a PC with Elipse SCADA to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.

Example

In the following example a configuration with Elipse SCADA is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.

The following addresses were chosen in the example:

IP addresses: IP addresses:

Station Address
HMI station 192.168.10.122
IBHLink S5++ 192.168.10.125

Operation with S7 HMI devices: For the operation with S7 HMI devices the following settings need to be made:

IP address of the PLC IP address of the IBH Link S5++
Rack number of the PLC 0
Slot number of the PLC 2
MPI® address of the PLC 2

Configuration:

The ethernet communication driver for S7-300/400 named MProt.dll must be selected witin the Application Organizer:

Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address>


Enter the IP Address of the IBH LinkS5 ++ and choose port 102:

Now the N an P Parameters must be set. The description you'll find within the helpfile <mprot_us.chm>
In the sample DB1.DB0 is chosen:

The configuration is now completed and the Tags can be used: