Difference between revisions of "IBHLink S5++:SIMATIC® S5 Elipse SCADA"
(Created page with "It is possible to realize a connection from a PC with '''Elipse SCADA''' to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway. ==Example== In the following ...") |
|||
Line 7: | Line 7: | ||
The following addresses were chosen in the example: | The following addresses were chosen in the example: | ||
+ | IP addresses: | ||
IP addresses: | IP addresses: | ||
{| class="wikitable" | {| class="wikitable" | ||
Line 14: | Line 15: | ||
| HMI station || 192.168.10.122 | | HMI station || 192.168.10.122 | ||
|- | |- | ||
− | | IBHLink | + | | IBHLink S5++ || 192.168.10.125 |
|} | |} | ||
− | + | '''Operation with S7 HMI devices:''' | |
+ | For the operation with S7 HMI devices the following settings need to be made: | ||
{| class="wikitable" | {| class="wikitable" | ||
|- | |- | ||
− | + | | IP address of the PLC || IP address of the IBH Link S5++ | |
|- | |- | ||
− | | | + | | Rack number of the PLC || 0 |
|- | |- | ||
− | | | + | | Slot number of the PLC || 2 |
+ | |- | ||
+ | | MPI® address of the PLC || 2 | ||
|} | |} | ||
− | |||
Configuration: | Configuration: | ||
Line 36: | Line 39: | ||
− | Enter the IP Address of the IBH | + | Enter the IP Address of the IBH LinkS5 ++ and choose port 102:<br /> |
[[Image:Elipse_driver_settings_ethernet.png|456px]] | [[Image:Elipse_driver_settings_ethernet.png|456px]] |
Revision as of 15:19, 18 June 2012
It is possible to realize a connection from a PC with Elipse SCADA to a S7-300/400 station over ethernet using an IBHLink S7++ as gateway.
Example
In the following example a configuration with Elipse SCADA is shown. The HMI station is connected to the IBHLink S7++ via an Ethernet connection. The IBHLink S7++ itself is connected to a S7-300/S7-400 station by MPI or PROFIBUS. Bus parameters were configured by the IBHNet configuration tool.
The following addresses were chosen in the example:
IP addresses: IP addresses:
Station | Address |
---|---|
HMI station | 192.168.10.122 |
IBHLink S5++ | 192.168.10.125 |
Operation with S7 HMI devices: For the operation with S7 HMI devices the following settings need to be made:
IP address of the PLC | IP address of the IBH Link S5++ |
Rack number of the PLC | 0 |
Slot number of the PLC | 2 |
MPI® address of the PLC | 2 |
Configuration:
The ethernet communication driver for S7-300/400 named MProt.dll must be selected witin the Application Organizer:
Within the MProt settings the MPI/DP address of the PLC has to be entered as <Default slave address>
Enter the IP Address of the IBH LinkS5 ++ and choose port 102:
Now the N an P Parameters must be set. The description you'll find within the helpfile <mprot_us.chm>
In the sample DB1.DB0 is chosen:
The configuration is now completed and the Tags can be used: