Reads a value from ''S7-SoftPLC''.
 
Reads a value from ''S7-SoftPLC''.
 +
  
 
{|
 
{|
Line 48: Line 49:
  
 
Writes a value in ''S7-SoftPLC''.
 
Writes a value in ''S7-SoftPLC''.
 +
  
 
{|
 
{|
Line 70: Line 72:
  
 
Reads multiple values from ''S7-SoftPLC''.
 
Reads multiple values from ''S7-SoftPLC''.
 +
  
 
{|
 
{|
Line 95: Line 98:
  
 
Writes multiple values to ''S7-SoftPLC''.
 
Writes multiple values to ''S7-SoftPLC''.
 +
  
 
{|
 
{|
Line 120: Line 124:
  
 
Reads the content of a data block from ''S7-SoftPLC''.
 
Reads the content of a data block from ''S7-SoftPLC''.
 +
  
 
{|
 
{|
Line 143: Line 148:
  
 
Writes a data block to ''S7-SoftPLC''.
 
Writes a data block to ''S7-SoftPLC''.
 +
  
 
{|
 
{|
Line 167: Line 173:
  
 
Reads the content of a S7 data block from the PLC (byte oriented).
 
Reads the content of a S7 data block from the PLC (byte oriented).
 +
  
 
{|
 
{|
Line 186: Line 193:
  
 
Writes the content of a S7 data block in the PLC (byte-oriented).
 
Writes the content of a S7 data block in the PLC (byte-oriented).
 +
  
 
{|
 
{|

Revision as of 11:53, 19 December 2012

Data interface to S7-SoftPLC

S7-SoftPLC can be accessed directly by various high level languages (e.g. Visual Basic®, Visual C/C++® or Borland C++Builder®). The DLL required for this (PLC32.DLL) is installed with S7-SoftPLC. The PLC32.DLL is a 32 Bit application.

Below the available functions for a data exchange are described.

Data transmitting functions

Read a single value

Reads a value from S7-SoftPLC.


unsigned long int DLLexport ReadVal (unsigned long int type,
unsigned long int no,
unsigned long int DBNo,
unsigned long int size,
unsigned long int far * val);,


Parameter Description Comment
type 'I' = input
'Q' = output
'M' = flag
'C' = counter value
'T' = timer value
'D' = data word or double data word
'B' = data bit, word, double word on
byte address
'P' = P_Parameter



16-bit-access only
16-bit-access only
depending on size
depending on size
compatible to S7 only
S7 from version 3 only
no adress Byte address of read in operand
DBNo Number of data block 1 – 16383
size Number of bits
0..7= bit no 0 7
8 = 1 byte
16 = 1 word
32 = 1 double word


'I','Q','M' only
val Read value Pointer to a valid variable in the user applications address space
Rückgabe 0 on Error Error messages

Length of parameter list (Visual-C): 20 bytes.


Write a single value

Writes a value in S7-SoftPLC.


unsigned long int DLLexport WriteVal (unsigned long int type,
unsigned long int no,
unsigned long int DBNo,
unsigned long int size,
unsigned long int far * val);,

TABLE

Length of parameter list (Visual-C): 20 bytes.


Read multiple values

Reads multiple values from S7-SoftPLC.


unsigned long int DLLexport ReadVals (unsigned long int type,
unsigned long int no,
unsigned long int DBNo,
unsigned long int size,
unsigned long int far * vals);,

TABLE

Length of parameter list (Visual-C): 20 bytes.


WARNING: FOR DATA BLOCKS (TYPE 'D') THE ARRAY HAS TO BE TWICE AS BIG, SINCE 2 BYTES ARE NECESSARY FOR EVERY DATA WORD!


Write multiple values

Writes multiple values to S7-SoftPLC.


unsigned long int DLLexport WriteVals (unsigned long int type,
unsigned long int no,
unsigned long int DBNo,
unsigned long int size,
unsigned long int far * vals);,

TABLE

Length of parameter list (Visual-C): 20 bytes.


WARNING: FOR DATA BLOCKS (TYPE = D) THE ARRAY HAS TO BE TWICE AS BIG, SINCE 2 BYTES ARE NECESSARY FOR EVERY DATA WORD!


Read DB

Reads the content of a data block from S7-SoftPLC.


unsigned long int DLLexport ReadDB (unsigned long int no,
unsigned short int far * block,
unsigned long int far * size,
unsigned long int synchronous);

TABLE

Length of parameter list (Visual-C): 16 bytes.


WARNING: WORD-ORIENTED READING, LOW- AND HIGH-BYTE ARE SWAPPED.


Write DB

Writes a data block to S7-SoftPLC.


unsigned long int DLLexport WriteDB (unsigned long int no,
unsigned short int far * block,
unsigned long int far * size,
unsigned long int synchronous);


TABLE

Length of parameter list (Visual-C): 16 bytes.


WARNING: WORD-ORIENTED READING, LOW- AND HIGH-BYTE ARE SWAPPED.


Read S7 DB

Reads the content of a S7 data block from the PLC (byte oriented).


unsigned long int DLLexport ReadDB_S7 (unsigned long int no,
unsigned char int far * block,
unsigned long int far * size,


TABLE

Length of parameter list (Visual-C): 12 bytes.


Write S7 DB

Writes the content of a S7 data block in the PLC (byte-oriented).


unsigned long int DLLexport WriteDB_S7 (unsigned long int no,
unsigned char int far * block,
unsigned long int far * size,

TABLE

Length of parameter list (Visual-C): 12 bytes.


Functions for data conversion

FloatToMC5

Converts floating point numbers from IBM-PC-format into S7 double words.

void DLLexport FloatToMC5 (float FloatValue,
unsigned long far * MC5Val);

TABLE


MC5ToFloat

Converts S7 double words into floating point numbers in IBM-PC-format.

void DLLexport MC5ToFloat (unsigned long far * MC5Val
float FloatVal);

TABLE


Accessing with a web server

If you are intending to access S7-SoftPLC with web applications(IIS), which should have access to the process data, please contact our support for examples. The S7-SoftPLC installs an object, which allows data access from script languages (VB Sript, J Script).