Configuration of the IBH Link UA with STEP7
Example
In the following example the configuration with STEP7 is shown.
The S7 IM151-8 station is connected with the IBH Link UA via Ethernet.
The following addresses were chosen in the example:
IP addresses:
Station | Address |
---|---|
IBHLink UA | 192.168.10.125 |
S7-1500 | 192.168.10.129 |
Configuration:
A new device will be added (in the sample a S7 IM151-8) and networked with Ethernet(1):
Now a DB can be created:
In our sample the symbols Data and Flagword 1 are defined within the symbolic table:
Within OB1 the data word 1 and flag word 1 will be counted in our example:
After downloading the blocks OB1 and DB1 to the IM151-8 a Simatic PC Station must be added:
Within the properties of the Ethernet Port of the PC Station, the IP address of the IBH Links UA must be entered
after adding an OPC Server in slot 1 and an IE-module in slot 2
Now a S7 connection between the OPC Server and the PC station must be established:
Within the properies of the OPC Server at <General> <S7> <OPC tags > the OPC Tags can be selected:
Now the configuration needs to be downloaded to the PLC and the IBH Link UA:
The configuration is now completed and the tags from the IBH link UA are available.
STEP7 Sample: IBH Link UA with SIMATIC S5 via IBH Link S5++
Download: STEP7 Sample: IBH Link UA S5