Difference between revisions of "OPCServer:Create Variables manually with Intouch"

From IBHsoftec Wiki English
Jump to: navigation, search
(Created page with "== Intouch® with the IBHsoftec OPC Server V4.x == === HOWTO create variables manually === Please run the Intouch® programm '''OPCLink'''. Select <Configure> <...")
 
 
(One intermediate revision by one other user not shown)
Line 1: Line 1:
== Intouch® with the IBHsoftec OPC Server V4.x ==
+
== Intouch with the IBHsoftec OPC Server V4.x ==
  
 
=== HOWTO create variables manually ===
 
=== HOWTO create variables manually ===
Line 6: Line 6:
  
  
Please run the Intouch® programm '''OPCLink'''.
+
Please run the Intouch programm '''OPCLink'''.
  
 
Select &lt;Configure&gt; &lt;Topic Defintions&gt;
 
Select &lt;Configure&gt; &lt;Topic Defintions&gt;

Latest revision as of 14:19, 19 September 2013

Intouch with the IBHsoftec OPC Server V4.x

HOWTO create variables manually

Please run the Intouch programm OPCLink.

Select <Configure> <Topic Defintions>

OPC InTouch man1.jpg


OPC InTouch man2.jpg


Define a topic Name (i.e. IBH_OPC ).

In the entry field OPC Server Name please select the server IBHSoftec.IBHOPC.DA.1.

The entry OPC Path must stay empty.

Please run the Intouch WindowMaker:

Create a new access name :


OPC InTouch man3.jpg


OPC InTouch man4.jpg


Select the newly created access name.

The entry <Item> consists of :

<D><Access-Path>.<Item Name>

In our sample : DS7_300.M1.0

Whereby the <D> is the notation for Discrete.

Following values are possible :

d discrete value
i integer value
r real value
m message value

The <Access-Path> represents the name of the <PLC>, which has been created in the IBH OPC Editor:


ProTool6 3.jpg


OPC InTouch man6.jpg


The OPC variables may now be used in the WindowMaker.